⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.01%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.04V (1.05%)
Voltage at Load End475.1 VLoss: 4.86 V (378.7 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A19.55 V (4.07%)460.4 V32.25 V (6.72%)1524.1 WDrop/Amp High
12 AWG3.31 mm²20 A12.29 V (2.56%)467.7 V20.27 V (4.22%)957.7 WDrop/Amp High
10 AWG5.26 mm²30 A7.73 V (1.61%)472.3 V12.75 V (2.66%)602.7 WDrop/Amp High
8 AWG8.37 mm²50 A4.86 V (1.01%)475.1 V8.02 V (1.67%)378.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.06 V (0.64%)476.9 V5.04 V (1.05%)238.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.92 V (0.4%)478.1 V3.17 V (0.66%)149.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.52 V (0.32%)478.5 V2.52 V (0.52%)118.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.21 V (0.25%)478.8 V2.0 V (0.42%)94.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.96 V (0.2%)479.0 V1.58 V (0.33%)74.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.76 V (0.16%)479.2 V1.25 V (0.26%)59.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.6 V (0.13%)479.4 V0.99 V (0.21%)47.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.48 V (0.1%)479.5 V0.79 V (0.16%)37.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.38 V (0.08%)479.6 V0.63 V (0.13%)29.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.32 V (0.07%)479.7 V0.53 V (0.11%)25.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (0.06%)479.7 V0.44 V (0.09%)20.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.23 V (0.05%)479.8 V0.38 V (0.08%)17.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.2 V (0.04%)479.8 V0.33 V (0.07%)15.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.03%)479.8 V0.26 V (0.06%)12.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.13 V (0.03%)479.9 V0.22 V (0.05%)10.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.02%)479.9 V0.18 V (0.04%)8.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.02%)479.9 V0.13 V (0.03%)6.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 80 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 4.86V (1.01%) and delivers 475.1V at the load.

What size aluminum wire is required for 45 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.04V (1.05%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.