🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.52%
Aluminum Wire (≤3% Drop)6 AWGDrop: 7.57V (1.58%)
Voltage at Load End472.7 VLoss: 7.29 V (568.1 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A29.33 V (6.11%)450.7 V48.38 V (10.08%)2286.1 WDrop/Amp High
12 AWG3.31 mm²20 A18.43 V (3.84%)461.6 V30.4 V (6.33%)1436.6 WDrop/Amp High
10 AWG5.26 mm²30 A11.6 V (2.42%)468.4 V19.13 V (3.99%)904.0 WDrop/Amp High
8 AWG8.37 mm²50 A7.29 V (1.52%)472.7 V12.02 V (2.5%)568.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.59 V (0.96%)475.4 V7.57 V (1.58%)357.5 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.88 V (0.6%)477.1 V4.76 V (0.99%)224.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.29 V (0.48%)477.7 V3.77 V (0.79%)178.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.81 V (0.38%)478.2 V2.99 V (0.62%)141.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.44 V (0.3%)478.6 V2.37 V (0.49%)112.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.14 V (0.24%)478.9 V1.88 V (0.39%)88.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.9 V (0.19%)479.1 V1.49 V (0.31%)70.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.72 V (0.15%)479.3 V1.18 V (0.25%)55.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.57 V (0.12%)479.4 V0.94 V (0.2%)44.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.48 V (0.1%)479.5 V0.79 V (0.17%)37.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.4 V (0.08%)479.6 V0.66 V (0.14%)31.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.34 V (0.07%)479.7 V0.57 V (0.12%)26.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.3 V (0.06%)479.7 V0.5 V (0.1%)23.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.24 V (0.05%)479.8 V0.4 V (0.08%)18.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.2 V (0.04%)479.8 V0.33 V (0.07%)15.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.16 V (0.03%)479.8 V0.26 V (0.06%)12.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.03%)479.9 V0.2 V (0.04%)9.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 120 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 7.29V (1.52%) and delivers 472.7V at the load.

What size aluminum wire is required for 45 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 7.57V (1.58%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.