⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.58%
Aluminum Wire (≤3% Drop)6 AWGDrop: 7.88V (1.64%)
Voltage at Load End472.4 VLoss: 7.59 V (591.8 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A30.55 V (6.37%)449.4 V50.4 V (10.5%)2381.3 WDrop/Amp High
12 AWG3.31 mm²20 A19.2 V (4.0%)460.8 V31.67 V (6.6%)1496.4 WDrop/Amp High
10 AWG5.26 mm²30 A12.08 V (2.52%)467.9 V19.93 V (4.15%)941.7 WDrop/Amp High
8 AWG8.37 mm²50 A7.59 V (1.58%)472.4 V12.52 V (2.61%)591.8 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.78 V (1.0%)475.2 V7.88 V (1.64%)372.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.0 V (0.63%)477.0 V4.96 V (1.03%)234.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.38 V (0.5%)477.6 V3.93 V (0.82%)185.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.89 V (0.39%)478.1 V3.12 V (0.65%)147.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.5 V (0.31%)478.5 V2.47 V (0.51%)116.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.19 V (0.25%)478.8 V1.96 V (0.41%)92.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.94 V (0.2%)479.1 V1.55 V (0.32%)73.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.75 V (0.16%)479.3 V1.23 V (0.26%)58.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.59 V (0.12%)479.4 V0.98 V (0.2%)46.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.5 V (0.1%)479.5 V0.83 V (0.17%)39.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.42 V (0.09%)479.6 V0.69 V (0.14%)32.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.36 V (0.07%)479.6 V0.59 V (0.12%)27.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.31 V (0.07%)479.7 V0.52 V (0.11%)24.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.25 V (0.05%)479.7 V0.41 V (0.09%)19.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.21 V (0.04%)479.8 V0.34 V (0.07%)16.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.17 V (0.03%)479.8 V0.28 V (0.06%)13.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.13 V (0.03%)479.9 V0.21 V (0.04%)9.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 125 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 7.59V (1.58%) and delivers 472.4V at the load.

What size aluminum wire is required for 45 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 7.88V (1.64%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.