🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 20 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.25%
Aluminum Wire (≤3% Drop)6 AWGDrop: 1.26V (0.26%)
Voltage at Load End478.8 VLoss: 1.21 V (94.7 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 20 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4.89 V (1.02%)475.1 V8.06 V (1.68%)381.0 WDrop/Amp High
12 AWG3.31 mm²20 A3.07 V (0.64%)476.9 V5.07 V (1.06%)239.4 WDrop/Amp High
10 AWG5.26 mm²30 A1.93 V (0.4%)478.1 V3.19 V (0.66%)150.7 WDrop/Amp High
8 AWG8.37 mm²50 A1.21 V (0.25%)478.8 V2.0 V (0.42%)94.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.76 V (0.16%)479.2 V1.26 V (0.26%)59.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.48 V (0.1%)479.5 V0.79 V (0.17%)37.5 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.38 V (0.08%)479.6 V0.63 V (0.13%)29.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.3 V (0.06%)479.7 V0.5 V (0.1%)23.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.24 V (0.05%)479.8 V0.4 V (0.08%)18.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.19 V (0.04%)479.8 V0.31 V (0.07%)14.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.15 V (0.03%)479.8 V0.25 V (0.05%)11.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.12 V (0.02%)479.9 V0.2 V (0.04%)9.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.09 V (0.02%)479.9 V0.16 V (0.03%)7.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.08 V (0.02%)479.9 V0.13 V (0.03%)6.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.07 V (0.01%)479.9 V0.11 V (0.02%)5.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.06 V (0.01%)479.9 V0.09 V (0.02%)4.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.05 V (0.01%)479.9 V0.08 V (0.02%)3.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.04 V (0.01%)480.0 V0.07 V (0.01%)3.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.03 V (0.01%)480.0 V0.06 V (0.01%)2.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.01%)480.0 V0.04 V (0.01%)2.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.0%)480.0 V0.03 V (0.01%)1.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 20 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 20 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 1.21V (0.25%) and delivers 478.8V at the load.

What size aluminum wire is required for 45 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 1.26V (0.26%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.