⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 0.38%
Aluminum Wire (≤3% Drop)6 AWGDrop: 1.89V (0.39%)
Voltage at Load End478.2 VLoss: 1.82 V (142.0 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A7.33 V (1.53%)472.7 V12.1 V (2.52%)571.5 WDrop/Amp High
12 AWG3.31 mm²20 A4.61 V (0.96%)475.4 V7.6 V (1.58%)359.1 WDrop/Amp High
10 AWG5.26 mm²30 A2.9 V (0.6%)477.1 V4.78 V (1.0%)226.0 WDrop/Amp High
8 AWG8.37 mm²50 A1.82 V (0.38%)478.2 V3.01 V (0.63%)142.0 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.15 V (0.24%)478.9 V1.89 V (0.39%)89.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.72 V (0.15%)479.3 V1.19 V (0.25%)56.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.57 V (0.12%)479.4 V0.94 V (0.2%)44.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.45 V (0.09%)479.5 V0.75 V (0.16%)35.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.36 V (0.07%)479.6 V0.59 V (0.12%)28.0 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.29 V (0.06%)479.7 V0.47 V (0.1%)22.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.23 V (0.05%)479.8 V0.37 V (0.08%)17.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.18 V (0.04%)479.8 V0.3 V (0.06%)14.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.14 V (0.03%)479.9 V0.23 V (0.05%)11.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.12 V (0.03%)479.9 V0.2 V (0.04%)9.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.1 V (0.02%)479.9 V0.17 V (0.03%)7.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.09 V (0.02%)479.9 V0.14 V (0.03%)6.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.08 V (0.02%)479.9 V0.12 V (0.03%)5.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.01%)479.9 V0.1 V (0.02%)4.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.01%)479.9 V0.08 V (0.02%)3.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.01%)480.0 V0.07 V (0.01%)3.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)480.0 V0.05 V (0.01%)2.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 30 feet one-way at 480V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 1.82V (0.38%) and delivers 478.2V at the load.

What size aluminum wire is required for 45 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 1.89V (0.39%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.