⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 750 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.43V (11.94%)
Voltage at Load End11.7 VLoss: 0.29 V (13.0 W)
Power & Breaker (125%)0.54 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 750 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A211.67 V (1763.96%)0.0 V349.16 V (2909.7%)9525.4 WDrop/Amp High
12 AWG3.31 mm²20 A133.02 V (1108.47%)0.0 V219.41 V (1828.45%)5985.7 WDrop/Amp High
10 AWG5.26 mm²30 A83.7 V (697.53%)0.0 V138.07 V (1150.61%)3766.7 WDrop/Amp High
8 AWG8.37 mm²50 A52.6 V (438.35%)0.0 V86.77 V (723.08%)2367.1 WDrop/Amp High
6 AWG13.3 mm²65 A33.1 V (275.87%)0.0 V54.61 V (455.05%)1489.7 WDrop/Amp High
4 AWG21.15 mm²85 A20.82 V (173.48%)0.0 V34.34 V (286.16%)936.8 WDrop/Amp High
3 AWG26.67 mm²100 A16.51 V (137.57%)0.0 V27.23 V (226.93%)742.9 WDrop/Amp High
2 AWG33.62 mm²115 A13.1 V (109.13%)0.0 V21.6 V (180.02%)589.3 WDrop/Amp High
1 AWG42.41 mm²130 A10.38 V (86.51%)1.6 V17.12 V (142.71%)467.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.23 V (68.59%)3.8 V13.58 V (113.15%)370.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.53 V (54.41%)5.5 V10.77 V (89.76%)293.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.18 V (43.16%)6.8 V8.54 V (71.19%)233.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.11 V (34.23%)7.9 V6.77 V (56.46%)184.8 WDrop/Amp High
250 kcmil126.7 mm²255 A3.48 V (28.96%)8.5 V5.73 V (47.77%)156.4 WDrop/Amp High
300 kcmil152.0 mm²285 A2.9 V (24.14%)9.1 V4.78 V (39.82%)130.3 WDrop/Amp High
350 kcmil177.3 mm²310 A2.48 V (20.69%)9.5 V4.1 V (34.14%)111.7 WDrop/Amp High
400 kcmil202.7 mm²335 A2.17 V (18.1%)9.8 V3.58 V (29.86%)97.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.74 V (14.48%)10.3 V2.87 V (23.88%)78.2 WDrop/Amp High
600 kcmil304.0 mm²420 A1.45 V (12.07%)10.6 V2.39 V (19.91%)65.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.16 V (9.66%)10.8 V1.91 V (15.93%)52.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.87 V (7.24%)11.1 V1.43 V (11.94%)39.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 750 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 750 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.41%) and delivers 11.7V at the load.

What size aluminum wire is required for 45 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.43V (11.94%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.