⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.41V (2.59%)
Voltage at Load End470.0 VLoss: 10.03 V (7820.8 W)
Power & Breaker (125%)374.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1833.16 V (381.91%)0.0 V3023.85 V (629.97%)1428805.0 WDrop/Amp High
12 AWG3.31 mm²20 A1151.95 V (239.99%)0.0 V1900.19 V (395.87%)897859.3 WDrop/Amp High
10 AWG5.26 mm²30 A724.9 V (151.02%)0.0 V1195.74 V (249.11%)565002.7 WDrop/Amp High
8 AWG8.37 mm²50 A455.55 V (94.91%)24.4 V751.45 V (156.55%)355067.4 WDrop/Amp High
6 AWG13.3 mm²65 A286.69 V (59.73%)193.3 V472.9 V (98.52%)223452.2 WDrop/Amp High
4 AWG21.15 mm²85 A180.28 V (37.56%)299.7 V297.38 V (61.95%)140516.0 WDrop/Amp High
3 AWG26.67 mm²100 A142.97 V (29.79%)337.0 V235.83 V (49.13%)111432.9 WDrop/Amp High
2 AWG33.62 mm²115 A113.41 V (23.63%)366.6 V187.08 V (38.97%)88397.2 WDrop/Amp High
1 AWG42.41 mm²130 A89.91 V (18.73%)390.1 V148.31 V (30.9%)70075.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A71.28 V (14.85%)408.7 V117.58 V (24.5%)55560.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A56.55 V (11.78%)423.5 V93.28 V (19.43%)44074.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A44.85 V (9.34%)435.1 V73.99 V (15.41%)34959.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A35.57 V (7.41%)444.4 V58.67 V (12.22%)27723.1 WDrop/Amp High
250 kcmil126.7 mm²255 A30.09 V (6.27%)449.9 V49.64 V (10.34%)23456.3 WDrop/Amp High
300 kcmil152.0 mm²285 A25.09 V (5.23%)454.9 V41.38 V (8.62%)19552.1 WDrop/Amp High
350 kcmil177.3 mm²310 A21.51 V (4.48%)458.5 V35.47 V (7.39%)16762.1 WDrop/Amp High
400 kcmil202.7 mm²335 A18.81 V (3.92%)461.2 V31.03 V (6.46%)14661.6 WDrop/Amp High
500 kcmil253.4 mm²380 A15.05 V (3.13%)465.0 V24.82 V (5.17%)11728.2 WDrop/Amp High
600 kcmil304.0 mm²420 A12.54 V (2.61%)467.5 V20.69 V (4.31%)9776.0 WDrop/Amp High
750 kcmil380.0 mm²475 A10.03 V (2.09%)470.0 V16.55 V (3.45%)7820.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A7.53 V (1.57%)472.5 V12.41 V (2.59%)5865.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 750 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 10.03V (2.09%) and delivers 470.0V at the load.

What size aluminum wire is required for 450 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.41V (2.59%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.