🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.35%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.1V (0.44%)
Voltage at Load End478.3 VLoss: 1.69 V (1394.2 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A309.6 V (64.5%)170.4 V510.7 V (106.39%)254715.4 WDrop/Amp High
12 AWG3.31 mm²20 A194.55 V (40.53%)285.4 V320.92 V (66.86%)160062.8 WDrop/Amp High
10 AWG5.26 mm²30 A122.43 V (25.51%)357.6 V201.95 V (42.07%)100723.9 WDrop/Amp High
8 AWG8.37 mm²50 A76.94 V (16.03%)403.1 V126.91 V (26.44%)63298.4 WDrop/Amp High
6 AWG13.3 mm²65 A48.42 V (10.09%)431.6 V79.87 V (16.64%)39835.2 WDrop/Amp High
4 AWG21.15 mm²85 A30.45 V (6.34%)449.6 V50.22 V (10.46%)25050.0 WDrop/Amp High
3 AWG26.67 mm²100 A24.15 V (5.03%)455.9 V39.83 V (8.3%)19865.3 WDrop/Amp High
2 AWG33.62 mm²115 A19.15 V (3.99%)460.8 V31.6 V (6.58%)15758.7 WDrop/Amp High
1 AWG42.41 mm²130 A15.18 V (3.16%)464.8 V25.05 V (5.22%)12492.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.04 V (2.51%)468.0 V19.86 V (4.14%)9904.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.55 V (1.99%)470.4 V15.75 V (3.28%)7857.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.58 V (1.58%)472.4 V12.5 V (2.6%)6232.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.01 V (1.25%)474.0 V9.91 V (2.06%)4942.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.08 V (1.06%)474.9 V8.38 V (1.75%)4181.6 WDrop/Amp High
300 kcmil152.0 mm²285 A4.24 V (0.88%)475.8 V6.99 V (1.46%)3485.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.63 V (0.76%)476.4 V5.99 V (1.25%)2988.2 WDrop/Amp High
400 kcmil202.7 mm²335 A3.18 V (0.66%)476.8 V5.24 V (1.09%)2613.8 WDrop/Amp High
500 kcmil253.4 mm²380 A2.54 V (0.53%)477.5 V4.19 V (0.87%)2090.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.12 V (0.44%)477.9 V3.49 V (0.73%)1742.8 WDrop/Amp High
750 kcmil380.0 mm²475 A1.69 V (0.35%)478.3 V2.8 V (0.58%)1394.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.27 V (0.26%)478.7 V2.1 V (0.44%)1045.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 120 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.69V (0.35%) and delivers 478.3V at the load.

What size aluminum wire is required for 475 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.1V (0.44%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.