⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 40 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.7V (0.15%)
Voltage at Load End479.4 VLoss: 0.56 V (464.7 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 40 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A103.2 V (21.5%)376.8 V170.23 V (35.46%)84905.1 WDrop/Amp High
12 AWG3.31 mm²20 A64.85 V (13.51%)415.1 V106.97 V (22.29%)53354.3 WDrop/Amp High
10 AWG5.26 mm²30 A40.81 V (8.5%)439.2 V67.32 V (14.02%)33574.6 WDrop/Amp High
8 AWG8.37 mm²50 A25.65 V (5.34%)454.4 V42.3 V (8.81%)21099.5 WDrop/Amp High
6 AWG13.3 mm²65 A16.14 V (3.36%)463.9 V26.62 V (5.55%)13278.4 WDrop/Amp High
4 AWG21.15 mm²85 A10.15 V (2.11%)469.9 V16.74 V (3.49%)8350.0 WDrop/Amp High
3 AWG26.67 mm²100 A8.05 V (1.68%)472.0 V13.28 V (2.77%)6621.8 WDrop/Amp High
2 AWG33.62 mm²115 A6.38 V (1.33%)473.6 V10.53 V (2.19%)5252.9 WDrop/Amp High
1 AWG42.41 mm²130 A5.06 V (1.05%)474.9 V8.35 V (1.74%)4164.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.01 V (0.84%)476.0 V6.62 V (1.38%)3301.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.18 V (0.66%)476.8 V5.25 V (1.09%)2619.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.53 V (0.53%)477.5 V4.17 V (0.87%)2077.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.0 V (0.42%)478.0 V3.3 V (0.69%)1647.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.69 V (0.35%)478.3 V2.79 V (0.58%)1393.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.41 V (0.29%)478.6 V2.33 V (0.49%)1161.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.21 V (0.25%)478.8 V2.0 V (0.42%)996.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.06 V (0.22%)478.9 V1.75 V (0.36%)871.3 WDrop/Amp High
500 kcmil253.4 mm²380 A0.85 V (0.18%)479.2 V1.4 V (0.29%)696.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.71 V (0.15%)479.3 V1.16 V (0.24%)580.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.56 V (0.12%)479.4 V0.93 V (0.19%)464.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.42 V (0.09%)479.6 V0.7 V (0.15%)348.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 40 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 40 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.56V (0.12%) and delivers 479.4V at the load.

What size aluminum wire is required for 475 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.7V (0.15%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.