🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 125 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.37%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.18V (0.45%)
Voltage at Load End478.2 VLoss: 1.77 V (1452.3 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 125 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A322.5 V (67.19%)157.5 V531.97 V (110.83%)265328.5 WDrop/Amp High
12 AWG3.31 mm²20 A202.66 V (42.22%)277.3 V334.29 V (69.64%)166732.1 WDrop/Amp High
10 AWG5.26 mm²30 A127.53 V (26.57%)352.5 V210.36 V (43.83%)104920.8 WDrop/Amp High
8 AWG8.37 mm²50 A80.14 V (16.7%)399.9 V132.2 V (27.54%)65935.9 WDrop/Amp High
6 AWG13.3 mm²65 A50.44 V (10.51%)429.6 V83.2 V (17.33%)41495.0 WDrop/Amp High
4 AWG21.15 mm²85 A31.72 V (6.61%)448.3 V52.32 V (10.9%)26093.8 WDrop/Amp High
3 AWG26.67 mm²100 A25.15 V (5.24%)454.8 V41.49 V (8.64%)20693.0 WDrop/Amp High
2 AWG33.62 mm²115 A19.95 V (4.16%)460.0 V32.91 V (6.86%)16415.3 WDrop/Amp High
1 AWG42.41 mm²130 A15.82 V (3.3%)464.2 V26.09 V (5.44%)13013.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.54 V (2.61%)467.5 V20.69 V (4.31%)10317.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.95 V (2.07%)470.1 V16.41 V (3.42%)8184.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.89 V (1.64%)472.1 V13.02 V (2.71%)6492.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.26 V (1.3%)473.7 V10.32 V (2.15%)5148.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.29 V (1.1%)474.7 V8.73 V (1.82%)4355.8 WDrop/Amp High
300 kcmil152.0 mm²285 A4.41 V (0.92%)475.6 V7.28 V (1.52%)3630.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.78 V (0.79%)476.2 V6.24 V (1.3%)3112.7 WDrop/Amp High
400 kcmil202.7 mm²335 A3.31 V (0.69%)476.7 V5.46 V (1.14%)2722.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.65 V (0.55%)477.4 V4.37 V (0.91%)2177.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.21 V (0.46%)477.8 V3.64 V (0.76%)1815.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.77 V (0.37%)478.2 V2.91 V (0.61%)1452.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.32 V (0.28%)478.7 V2.18 V (0.45%)1089.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 125 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 125 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.77V (0.37%) and delivers 478.2V at the load.

What size aluminum wire is required for 475 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.18V (0.45%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.