475 Amp Wire Size at 175 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.51%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.06V (0.64%)
Voltage at Load End477.5 VLoss: 2.47 V (2033.3 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 175 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A451.5 V (94.06%)28.5 V744.76 V (155.16%)371459.9 WDrop/Amp High
12 AWG3.31 mm²20 A283.72 V (59.11%)196.3 V468.01 V (97.5%)233424.9 WDrop/Amp High
10 AWG5.26 mm²30 A178.54 V (37.2%)301.5 V294.51 V (61.36%)146889.1 WDrop/Amp High
8 AWG8.37 mm²50 A112.2 V (23.38%)367.8 V185.08 V (38.56%)92310.2 WDrop/Amp High
6 AWG13.3 mm²65 A70.61 V (14.71%)409.4 V116.47 V (24.27%)58093.0 WDrop/Amp High
4 AWG21.15 mm²85 A44.4 V (9.25%)435.6 V73.24 V (15.26%)36531.3 WDrop/Amp High
3 AWG26.67 mm²100 A35.21 V (7.34%)444.8 V58.08 V (12.1%)28970.2 WDrop/Amp High
2 AWG33.62 mm²115 A27.93 V (5.82%)452.1 V46.08 V (9.6%)22981.5 WDrop/Amp High
1 AWG42.41 mm²130 A22.14 V (4.61%)457.9 V36.53 V (7.61%)18218.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.56 V (3.66%)462.4 V28.96 V (6.03%)14444.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.93 V (2.9%)466.1 V22.97 V (4.79%)11458.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.05 V (2.3%)469.0 V18.22 V (3.8%)9088.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.76 V (1.83%)471.2 V14.45 V (3.01%)7207.4 WDrop/Amp High
250 kcmil126.7 mm²255 A7.41 V (1.54%)472.6 V12.23 V (2.55%)6098.2 WDrop/Amp High
300 kcmil152.0 mm²285 A6.18 V (1.29%)473.8 V10.19 V (2.12%)5083.1 WDrop/Amp High
350 kcmil177.3 mm²310 A5.3 V (1.1%)474.7 V8.74 V (1.82%)4357.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.63 V (0.97%)475.4 V7.64 V (1.59%)3811.7 WDrop/Amp High
500 kcmil253.4 mm²380 A3.71 V (0.77%)476.3 V6.11 V (1.27%)3049.1 WDrop/Amp High
600 kcmil304.0 mm²420 A3.09 V (0.64%)476.9 V5.1 V (1.06%)2541.6 WDrop/Amp High
750 kcmil380.0 mm²475 A2.47 V (0.51%)477.5 V4.08 V (0.85%)2033.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.85 V (0.39%)478.1 V3.06 V (0.64%)1524.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 175 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 175 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.47V (0.51%) and delivers 477.5V at the load.

What size aluminum wire is required for 475 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.06V (0.64%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.