⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.88%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.62V (1.09%)
Voltage at Load End237.9 VLoss: 2.12 V (1742.8 W)
Power & Breaker (125%)197.45 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A387.0 V (161.25%)0.0 V638.37 V (265.99%)318394.2 WDrop/Amp High
12 AWG3.31 mm²20 A243.19 V (101.33%)0.0 V401.15 V (167.15%)200078.5 WDrop/Amp High
10 AWG5.26 mm²30 A153.03 V (63.76%)87.0 V252.43 V (105.18%)125904.9 WDrop/Amp High
8 AWG8.37 mm²50 A96.17 V (40.07%)143.8 V158.64 V (66.1%)79123.0 WDrop/Amp High
6 AWG13.3 mm²65 A60.52 V (25.22%)179.5 V99.84 V (41.6%)49794.0 WDrop/Amp High
4 AWG21.15 mm²85 A38.06 V (15.86%)201.9 V62.78 V (26.16%)31312.5 WDrop/Amp High
3 AWG26.67 mm²100 A30.18 V (12.58%)209.8 V49.79 V (20.74%)24831.6 WDrop/Amp High
2 AWG33.62 mm²115 A23.94 V (9.98%)216.1 V39.49 V (16.46%)19698.4 WDrop/Amp High
1 AWG42.41 mm²130 A18.98 V (7.91%)221.0 V31.31 V (13.05%)15615.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.05 V (6.27%)225.0 V24.82 V (10.34%)12381.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.94 V (4.97%)228.1 V19.69 V (8.2%)9821.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.47 V (3.95%)230.5 V15.62 V (6.51%)7790.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.51 V (3.13%)232.5 V12.39 V (5.16%)6177.8 WDrop/Amp High
250 kcmil126.7 mm²255 A6.35 V (2.65%)233.6 V10.48 V (4.37%)5227.0 WDrop/Amp High
300 kcmil152.0 mm²285 A5.3 V (2.21%)234.7 V8.74 V (3.64%)4357.0 WDrop/Amp High
350 kcmil177.3 mm²310 A4.54 V (1.89%)235.5 V7.49 V (3.12%)3735.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.97 V (1.65%)236.0 V6.55 V (2.73%)3267.2 WDrop/Amp High
500 kcmil253.4 mm²380 A3.18 V (1.32%)236.8 V5.24 V (2.18%)2613.5 WDrop/Amp High
600 kcmil304.0 mm²420 A2.65 V (1.1%)237.4 V4.37 V (1.82%)2178.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.12 V (0.88%)237.9 V3.49 V (1.46%)1742.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.59 V (0.66%)238.4 V2.62 V (1.09%)1307.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 150 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.12V (0.88%) and delivers 237.9V at the load.

What size aluminum wire is required for 475 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.62V (1.09%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.