🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.47%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.4V (0.58%)
Voltage at Load End238.9 VLoss: 1.13 V (929.5 W)
Power & Breaker (125%)197.45 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A206.4 V (86.0%)33.6 V340.46 V (141.86%)169810.2 WDrop/Amp High
12 AWG3.31 mm²20 A129.7 V (54.04%)110.3 V213.95 V (89.14%)106708.5 WDrop/Amp High
10 AWG5.26 mm²30 A81.62 V (34.01%)158.4 V134.63 V (56.1%)67149.3 WDrop/Amp High
8 AWG8.37 mm²50 A51.29 V (21.37%)188.7 V84.61 V (35.25%)42199.0 WDrop/Amp High
6 AWG13.3 mm²65 A32.28 V (13.45%)207.7 V53.25 V (22.19%)26556.8 WDrop/Amp High
4 AWG21.15 mm²85 A20.3 V (8.46%)219.7 V33.48 V (13.95%)16700.0 WDrop/Amp High
3 AWG26.67 mm²100 A16.1 V (6.71%)223.9 V26.55 V (11.06%)13243.5 WDrop/Amp High
2 AWG33.62 mm²115 A12.77 V (5.32%)227.2 V21.06 V (8.78%)10505.8 WDrop/Amp High
1 AWG42.41 mm²130 A10.12 V (4.22%)229.9 V16.7 V (6.96%)8328.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.03 V (3.34%)232.0 V13.24 V (5.52%)6603.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.37 V (2.65%)233.6 V10.5 V (4.38%)5238.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.05 V (2.1%)234.9 V8.33 V (3.47%)4154.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.0 V (1.67%)236.0 V6.61 V (2.75%)3294.8 WDrop/Amp High
250 kcmil126.7 mm²255 A3.39 V (1.41%)236.6 V5.59 V (2.33%)2787.7 WDrop/Amp High
300 kcmil152.0 mm²285 A2.82 V (1.18%)237.2 V4.66 V (1.94%)2323.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.42 V (1.01%)237.6 V3.99 V (1.66%)1992.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.12 V (0.88%)237.9 V3.49 V (1.46%)1742.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.69 V (0.71%)238.3 V2.79 V (1.16%)1393.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.41 V (0.59%)238.6 V2.33 V (0.97%)1161.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.13 V (0.47%)238.9 V1.86 V (0.78%)929.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.85 V (0.35%)239.2 V1.4 V (0.58%)697.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 80 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.13V (0.47%) and delivers 238.9V at the load.

What size aluminum wire is required for 475 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.4V (0.58%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.