🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 20 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.35V (0.15%)
Voltage at Load End239.7 VLoss: 0.28 V (232.4 W)
Power & Breaker (125%)197.45 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A51.6 V (21.5%)188.4 V85.12 V (35.46%)42452.6 WDrop/Amp High
12 AWG3.31 mm²20 A32.43 V (13.51%)207.6 V53.49 V (22.29%)26677.1 WDrop/Amp High
10 AWG5.26 mm²30 A20.4 V (8.5%)219.6 V33.66 V (14.02%)16787.3 WDrop/Amp High
8 AWG8.37 mm²50 A12.82 V (5.34%)227.2 V21.15 V (8.81%)10549.7 WDrop/Amp High
6 AWG13.3 mm²65 A8.07 V (3.36%)231.9 V13.31 V (5.55%)6639.2 WDrop/Amp High
4 AWG21.15 mm²85 A5.07 V (2.11%)234.9 V8.37 V (3.49%)4175.0 WDrop/Amp High
3 AWG26.67 mm²100 A4.02 V (1.68%)236.0 V6.64 V (2.77%)3310.9 WDrop/Amp High
2 AWG33.62 mm²115 A3.19 V (1.33%)236.8 V5.27 V (2.19%)2626.5 WDrop/Amp High
1 AWG42.41 mm²130 A2.53 V (1.05%)237.5 V4.17 V (1.74%)2082.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.01 V (0.84%)238.0 V3.31 V (1.38%)1650.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.59 V (0.66%)238.4 V2.63 V (1.09%)1309.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.26 V (0.53%)238.7 V2.08 V (0.87%)1038.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.0 V (0.42%)239.0 V1.65 V (0.69%)823.7 WDrop/Amp High
250 kcmil126.7 mm²255 A0.85 V (0.35%)239.2 V1.4 V (0.58%)696.9 WDrop/Amp High
300 kcmil152.0 mm²285 A0.71 V (0.29%)239.3 V1.16 V (0.49%)580.9 WDrop/Amp High
350 kcmil177.3 mm²310 A0.61 V (0.25%)239.4 V1.0 V (0.42%)498.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.53 V (0.22%)239.5 V0.87 V (0.36%)435.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.42 V (0.18%)239.6 V0.7 V (0.29%)348.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.35 V (0.15%)239.6 V0.58 V (0.24%)290.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.28 V (0.12%)239.7 V0.47 V (0.19%)232.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.21 V (0.09%)239.8 V0.35 V (0.15%)174.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 20 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.28V (0.12%) and delivers 239.7V at the load.

What size aluminum wire is required for 475 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.35V (0.15%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.