475 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.7%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.37V (2.1%)
Voltage at Load End204.5 VLoss: 3.53 V (2904.6 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A645.0 V (310.1%)0.0 V1063.95 V (511.51%)530657.0 WDrop/Amp High
12 AWG3.31 mm²20 A405.32 V (194.86%)0.0 V668.58 V (321.43%)333464.2 WDrop/Amp High
10 AWG5.26 mm²30 A255.06 V (122.62%)0.0 V420.72 V (202.27%)209841.5 WDrop/Amp High
8 AWG8.37 mm²50 A160.29 V (77.06%)47.7 V264.4 V (127.11%)131871.7 WDrop/Amp High
6 AWG13.3 mm²65 A100.87 V (48.5%)107.1 V166.39 V (80.0%)82990.0 WDrop/Amp High
4 AWG21.15 mm²85 A63.43 V (30.5%)144.6 V104.63 V (50.3%)52187.5 WDrop/Amp High
3 AWG26.67 mm²100 A50.3 V (24.18%)157.7 V82.98 V (39.89%)41386.1 WDrop/Amp High
2 AWG33.62 mm²115 A39.9 V (19.19%)168.1 V65.82 V (31.65%)32830.7 WDrop/Amp High
1 AWG42.41 mm²130 A31.63 V (15.21%)176.4 V52.18 V (25.09%)26026.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.08 V (12.06%)182.9 V41.37 V (19.89%)20635.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.9 V (9.57%)188.1 V32.82 V (15.78%)16369.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.78 V (7.59%)192.2 V26.03 V (12.52%)12984.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.51 V (6.02%)195.5 V20.64 V (9.92%)10296.3 WDrop/Amp High
250 kcmil126.7 mm²255 A10.59 V (5.09%)197.4 V17.47 V (8.4%)8711.7 WDrop/Amp High
300 kcmil152.0 mm²285 A8.83 V (4.24%)199.2 V14.56 V (7.0%)7261.6 WDrop/Amp High
350 kcmil177.3 mm²310 A7.57 V (3.64%)200.4 V12.48 V (6.0%)6225.4 WDrop/Amp High
400 kcmil202.7 mm²335 A6.62 V (3.18%)201.4 V10.92 V (5.25%)5445.3 WDrop/Amp High
500 kcmil253.4 mm²380 A5.29 V (2.55%)202.7 V8.73 V (4.2%)4355.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.41 V (2.12%)203.6 V7.28 V (3.5%)3630.8 WDrop/Amp High
750 kcmil380.0 mm²475 A3.53 V (1.7%)204.5 V5.82 V (2.8%)2904.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.65 V (1.27%)205.4 V4.37 V (2.1%)2178.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 250 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.53V (1.7%) and delivers 204.5V at the load.

What size aluminum wire is required for 475 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.37V (2.1%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.