⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 350 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)12 AWG3.31 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)10 AWGDrop: 7.16V (2.98%)
Voltage at Load End233.1 VLoss: 6.9 V (34.5 W)
Power & Breaker (125%)1.2 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A10.98 V (4.57%)229.0 V18.1 V (7.54%)54.9 W~ ≤5%
12 AWG3.31 mm²20 A6.9 V (2.87%)233.1 V11.38 V (4.74%)34.5 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A4.34 V (1.81%)235.7 V7.16 V (2.98%)21.7 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A2.73 V (1.14%)237.3 V4.5 V (1.87%)13.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.72 V (0.72%)238.3 V2.83 V (1.18%)8.6 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.08 V (0.45%)238.9 V1.78 V (0.74%)5.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.86 V (0.36%)239.1 V1.41 V (0.59%)4.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.68 V (0.28%)239.3 V1.12 V (0.47%)3.4 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.54 V (0.22%)239.5 V0.89 V (0.37%)2.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.43 V (0.18%)239.6 V0.7 V (0.29%)2.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.34 V (0.14%)239.7 V0.56 V (0.23%)1.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.27 V (0.11%)239.7 V0.44 V (0.18%)1.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.21 V (0.09%)239.8 V0.35 V (0.15%)1.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.18 V (0.08%)239.8 V0.3 V (0.12%)0.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.15 V (0.06%)239.8 V0.25 V (0.1%)0.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.05%)239.9 V0.21 V (0.09%)0.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.11 V (0.05%)239.9 V0.19 V (0.08%)0.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.04%)239.9 V0.15 V (0.06%)0.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.03%)239.9 V0.12 V (0.05%)0.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.03%)239.9 V0.1 V (0.04%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)240.0 V0.07 V (0.03%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 350 feet one-way at 240V (1-Phase), you need 12 AWG copper wire. This produces a voltage drop of 6.9V (2.87%) and delivers 233.1V at the load.

What size aluminum wire is required for 5 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 10 AWG to maintain voltage drop at 7.16V (2.98%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.