⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 350 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 0.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.44V (1.34%)
Voltage at Load End476.1 VLoss: 3.9 V (3379.1 W)
Power & Breaker (125%)415.69 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 350 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A950.53 V (198.03%)0.0 V1567.92 V (326.65%)823179.8 WDrop/Amp High
12 AWG3.31 mm²20 A597.31 V (124.44%)0.0 V985.28 V (205.27%)517285.2 WDrop/Amp High
10 AWG5.26 mm²30 A375.87 V (78.31%)104.1 V620.02 V (129.17%)325516.0 WDrop/Amp High
8 AWG8.37 mm²50 A236.21 V (49.21%)243.8 V389.64 V (81.17%)204565.6 WDrop/Amp High
6 AWG13.3 mm²65 A148.65 V (30.97%)331.3 V245.21 V (51.09%)128737.9 WDrop/Amp High
4 AWG21.15 mm²85 A93.48 V (19.47%)386.5 V154.2 V (32.12%)80955.7 WDrop/Amp High
3 AWG26.67 mm²100 A74.13 V (15.44%)405.9 V122.28 V (25.48%)64200.0 WDrop/Amp High
2 AWG33.62 mm²115 A58.81 V (12.25%)421.2 V97.0 V (20.21%)50928.4 WDrop/Amp High
1 AWG42.41 mm²130 A46.62 V (9.71%)433.4 V76.9 V (16.02%)40372.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.96 V (7.7%)443.0 V60.97 V (12.7%)32010.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.32 V (6.11%)450.7 V48.37 V (10.08%)25392.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.26 V (4.85%)456.7 V38.36 V (7.99%)20141.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.44 V (3.84%)461.6 V30.42 V (6.34%)15972.1 WDrop/Amp High
250 kcmil126.7 mm²255 A15.6 V (3.25%)464.4 V25.74 V (5.36%)13513.9 WDrop/Amp High
300 kcmil152.0 mm²285 A13.01 V (2.71%)467.0 V21.46 V (4.47%)11264.6 WDrop/Amp High
350 kcmil177.3 mm²310 A11.15 V (2.32%)468.8 V18.39 V (3.83%)9657.2 WDrop/Amp High
400 kcmil202.7 mm²335 A9.75 V (2.03%)470.2 V16.09 V (3.35%)8447.0 WDrop/Amp High
500 kcmil253.4 mm²380 A7.8 V (1.63%)472.2 V12.87 V (2.68%)6757.0 WDrop/Amp High
600 kcmil304.0 mm²420 A6.5 V (1.35%)473.5 V10.73 V (2.23%)5632.3 WDrop/Amp High
750 kcmil380.0 mm²475 A5.2 V (1.08%)474.8 V8.58 V (1.79%)4505.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.9 V (0.81%)476.1 V6.44 V (1.34%)3379.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 350 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 350 feet one-way at 480V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 3.9V (0.81%) and delivers 476.1V at the load.

What size aluminum wire is required for 500 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.44V (1.34%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.