⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 1.05%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (1.72%)
Voltage at Load End475.0 VLoss: 5.02 V (4344.6 W)
Power & Breaker (125%)415.69 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1222.11 V (254.61%)0.0 V2015.9 V (419.98%)1058374.0 WDrop/Amp High
12 AWG3.31 mm²20 A767.97 V (159.99%)0.0 V1266.79 V (263.91%)665081.0 WDrop/Amp High
10 AWG5.26 mm²30 A483.27 V (100.68%)0.0 V797.16 V (166.08%)418520.5 WDrop/Amp High
8 AWG8.37 mm²50 A303.7 V (63.27%)176.3 V500.96 V (104.37%)263012.9 WDrop/Amp High
6 AWG13.3 mm²65 A191.13 V (39.82%)288.9 V315.27 V (65.68%)165520.2 WDrop/Amp High
4 AWG21.15 mm²85 A120.19 V (25.04%)359.8 V198.25 V (41.3%)104086.0 WDrop/Amp High
3 AWG26.67 mm²100 A95.31 V (19.86%)384.7 V157.22 V (32.75%)82542.9 WDrop/Amp High
2 AWG33.62 mm²115 A75.61 V (15.75%)404.4 V124.72 V (25.98%)65479.4 WDrop/Amp High
1 AWG42.41 mm²130 A59.94 V (12.49%)420.1 V98.87 V (20.6%)51908.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.52 V (9.9%)432.5 V78.39 V (16.33%)41155.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.7 V (7.85%)442.3 V62.18 V (12.96%)32647.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.9 V (6.23%)450.1 V49.32 V (10.28%)25896.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.71 V (4.94%)456.3 V39.11 V (8.15%)20535.6 WDrop/Amp High
250 kcmil126.7 mm²255 A20.06 V (4.18%)459.9 V33.09 V (6.89%)17375.0 WDrop/Amp High
300 kcmil152.0 mm²285 A16.72 V (3.48%)463.3 V27.59 V (5.75%)14483.0 WDrop/Amp High
350 kcmil177.3 mm²310 A14.34 V (2.99%)465.7 V23.65 V (4.93%)12416.3 WDrop/Amp High
400 kcmil202.7 mm²335 A12.54 V (2.61%)467.5 V20.69 V (4.31%)10860.5 WDrop/Amp High
500 kcmil253.4 mm²380 A10.03 V (2.09%)470.0 V16.55 V (3.45%)8687.5 WDrop/Amp High
600 kcmil304.0 mm²420 A8.36 V (1.74%)471.6 V13.79 V (2.87%)7241.5 WDrop/Amp High
750 kcmil380.0 mm²475 A6.69 V (1.39%)473.3 V11.03 V (2.3%)5793.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.02 V (1.05%)475.0 V8.28 V (1.72%)4344.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 450 feet one-way at 480V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.02V (1.05%) and delivers 475.0V at the load.

What size aluminum wire is required for 500 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (1.72%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.