⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 23.36V (9.73%)
Voltage at Load End232.9 VLoss: 7.08 V (3894.1 W)
Power & Breaker (125%)132.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3449.52 V (1437.3%)0.0 V5690.09 V (2370.87%)1897233.5 WDrop/Amp High
12 AWG3.31 mm²20 A2167.67 V (903.2%)0.0 V3575.64 V (1489.85%)1192219.2 WDrop/Amp High
10 AWG5.26 mm²30 A1364.07 V (568.36%)0.0 V2250.07 V (937.53%)750236.8 WDrop/Amp High
8 AWG8.37 mm²50 A857.23 V (357.18%)0.0 V1414.02 V (589.18%)471475.0 WDrop/Amp High
6 AWG13.3 mm²65 A539.47 V (224.78%)0.0 V889.88 V (370.78%)296710.2 WDrop/Amp High
4 AWG21.15 mm²85 A339.24 V (141.35%)0.0 V559.59 V (233.16%)186583.7 WDrop/Amp High
3 AWG26.67 mm²100 A269.03 V (112.1%)0.0 V443.77 V (184.9%)147965.7 WDrop/Amp High
2 AWG33.62 mm²115 A213.41 V (88.92%)26.6 V352.03 V (146.68%)117377.9 WDrop/Amp High
1 AWG42.41 mm²130 A169.18 V (70.49%)70.8 V279.07 V (116.28%)93049.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A134.14 V (55.89%)105.9 V221.26 V (92.19%)73775.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A106.41 V (44.34%)133.6 V175.52 V (73.13%)58523.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A84.4 V (35.17%)155.6 V139.22 V (58.01%)46421.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A66.93 V (27.89%)173.1 V110.4 V (46.0%)36812.0 WDrop/Amp High
250 kcmil126.7 mm²255 A56.63 V (23.6%)183.4 V93.41 V (38.92%)31146.4 WDrop/Amp High
300 kcmil152.0 mm²285 A47.2 V (19.67%)192.8 V77.86 V (32.44%)25962.1 WDrop/Amp High
350 kcmil177.3 mm²310 A40.47 V (16.86%)199.5 V66.75 V (27.81%)22257.4 WDrop/Amp High
400 kcmil202.7 mm²335 A35.4 V (14.75%)204.6 V58.39 V (24.33%)19468.4 WDrop/Amp High
500 kcmil253.4 mm²380 A28.31 V (11.8%)211.7 V46.71 V (19.46%)15573.2 WDrop/Amp High
600 kcmil304.0 mm²420 A23.6 V (9.83%)216.4 V38.93 V (16.22%)12981.1 WDrop/Amp High
750 kcmil380.0 mm²475 A18.88 V (7.87%)221.1 V31.15 V (12.98%)10384.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A14.16 V (5.9%)225.8 V23.36 V (9.73%)7788.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 1000 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 7.08V (2.95%) and delivers 232.9V at the load.

What size aluminum wire is required for 550 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 23.36V (9.73%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.