🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.37%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.53V (1.22%)
Voltage at Load End207.2 VLoss: 0.77 V (730.1 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A373.42 V (179.53%)0.0 V615.97 V (296.14%)355731.3 WDrop/Amp High
12 AWG3.31 mm²20 A234.66 V (112.82%)0.0 V387.07 V (186.09%)223541.1 WDrop/Amp High
10 AWG5.26 mm²30 A147.66 V (70.99%)60.3 V243.58 V (117.1%)140669.4 WDrop/Amp High
8 AWG8.37 mm²50 A92.8 V (44.61%)115.2 V153.07 V (73.59%)88401.6 WDrop/Amp High
6 AWG13.3 mm²65 A58.4 V (28.08%)149.6 V96.33 V (46.31%)55633.2 WDrop/Amp High
4 AWG21.15 mm²85 A36.72 V (17.66%)171.3 V60.58 V (29.12%)34984.4 WDrop/Amp High
3 AWG26.67 mm²100 A29.12 V (14.0%)178.9 V48.04 V (23.1%)27743.6 WDrop/Amp High
2 AWG33.62 mm²115 A23.1 V (11.11%)184.9 V38.11 V (18.32%)22008.4 WDrop/Amp High
1 AWG42.41 mm²130 A18.31 V (8.81%)189.7 V30.21 V (14.52%)17446.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.52 V (6.98%)193.5 V23.95 V (11.52%)13832.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.52 V (5.54%)196.5 V19.0 V (9.13%)10973.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.14 V (4.39%)198.9 V15.07 V (7.25%)8703.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.25 V (3.48%)200.8 V11.95 V (5.75%)6902.2 WDrop/Amp High
250 kcmil126.7 mm²255 A6.13 V (2.95%)201.9 V10.11 V (4.86%)5839.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.11 V (2.46%)202.9 V8.43 V (4.05%)4867.9 WDrop/Amp High
350 kcmil177.3 mm²310 A4.38 V (2.11%)203.6 V7.23 V (3.47%)4173.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.83 V (1.84%)204.2 V6.32 V (3.04%)3650.3 WDrop/Amp High
500 kcmil253.4 mm²380 A3.07 V (1.47%)204.9 V5.06 V (2.43%)2920.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.55 V (1.23%)205.4 V4.21 V (2.03%)2434.0 WDrop/Amp High
750 kcmil380.0 mm²475 A2.04 V (0.98%)206.0 V3.37 V (1.62%)1947.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.53 V (0.74%)206.5 V2.53 V (1.22%)1460.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 125 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.77V (0.37%) and delivers 207.2V at the load.

What size aluminum wire is required for 550 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.53V (1.22%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.