🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.29%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.02V (0.97%)
Voltage at Load End207.4 VLoss: 0.61 V (584.1 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A298.74 V (143.62%)0.0 V492.78 V (236.91%)284585.0 WDrop/Amp High
12 AWG3.31 mm²20 A187.73 V (90.25%)20.3 V309.66 V (148.87%)178832.9 WDrop/Amp High
10 AWG5.26 mm²30 A118.13 V (56.79%)89.9 V194.86 V (93.68%)112535.5 WDrop/Amp High
8 AWG8.37 mm²50 A74.24 V (35.69%)133.8 V122.46 V (58.87%)70721.2 WDrop/Amp High
6 AWG13.3 mm²65 A46.72 V (22.46%)161.3 V77.07 V (37.05%)44506.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.38 V (14.12%)178.6 V48.46 V (23.3%)27987.6 WDrop/Amp High
3 AWG26.67 mm²100 A23.3 V (11.2%)184.7 V38.43 V (18.48%)22194.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.48 V (8.89%)189.5 V30.49 V (14.66%)17606.7 WDrop/Amp High
1 AWG42.41 mm²130 A14.65 V (7.04%)193.3 V24.17 V (11.62%)13957.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.62 V (5.58%)196.4 V19.16 V (9.21%)11066.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.22 V (4.43%)198.8 V15.2 V (7.31%)8778.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.31 V (3.51%)200.7 V12.06 V (5.8%)6963.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.8 V (2.79%)202.2 V9.56 V (4.6%)5521.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.9 V (2.36%)203.1 V8.09 V (3.89%)4672.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.09 V (1.97%)203.9 V6.74 V (3.24%)3894.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.5 V (1.68%)204.5 V5.78 V (2.78%)3338.6 WDrop/Amp High
400 kcmil202.7 mm²335 A3.07 V (1.47%)204.9 V5.06 V (2.43%)2920.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.45 V (1.18%)205.5 V4.04 V (1.94%)2336.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.04 V (0.98%)206.0 V3.37 V (1.62%)1947.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.64 V (0.79%)206.4 V2.7 V (1.3%)1557.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.23 V (0.59%)206.8 V2.02 V (0.97%)1168.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 100 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.61V (0.29%) and delivers 207.4V at the load.

What size aluminum wire is required for 550 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.02V (0.97%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.