⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 40 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.81V (0.39%)
Voltage at Load End207.8 VLoss: 0.24 V (233.7 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 40 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A119.49 V (57.45%)88.5 V197.11 V (94.76%)113834.0 WDrop/Amp High
12 AWG3.31 mm²20 A75.09 V (36.1%)132.9 V123.86 V (59.55%)71533.2 WDrop/Amp High
10 AWG5.26 mm²30 A47.25 V (22.72%)160.7 V77.94 V (37.47%)45014.2 WDrop/Amp High
8 AWG8.37 mm²50 A29.7 V (14.28%)178.3 V48.98 V (23.55%)28288.5 WDrop/Amp High
6 AWG13.3 mm²65 A18.69 V (8.98%)189.3 V30.83 V (14.82%)17802.6 WDrop/Amp High
4 AWG21.15 mm²85 A11.75 V (5.65%)196.2 V19.38 V (9.32%)11195.0 WDrop/Amp High
3 AWG26.67 mm²100 A9.32 V (4.48%)198.7 V15.37 V (7.39%)8877.9 WDrop/Amp High
2 AWG33.62 mm²115 A7.39 V (3.55%)200.6 V12.19 V (5.86%)7042.7 WDrop/Amp High
1 AWG42.41 mm²130 A5.86 V (2.82%)202.1 V9.67 V (4.65%)5583.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.65 V (2.23%)203.4 V7.66 V (3.68%)4426.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.69 V (1.77%)204.3 V6.08 V (2.92%)3511.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.92 V (1.41%)205.1 V4.82 V (2.32%)2785.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.32 V (1.11%)205.7 V3.82 V (1.84%)2208.7 WDrop/Amp High
250 kcmil126.7 mm²255 A1.96 V (0.94%)206.0 V3.24 V (1.56%)1868.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.64 V (0.79%)206.4 V2.7 V (1.3%)1557.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.4 V (0.67%)206.6 V2.31 V (1.11%)1335.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.23 V (0.59%)206.8 V2.02 V (0.97%)1168.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.98 V (0.47%)207.0 V1.62 V (0.78%)934.4 WDrop/Amp High
600 kcmil304.0 mm²420 A0.82 V (0.39%)207.2 V1.35 V (0.65%)778.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.65 V (0.31%)207.3 V1.08 V (0.52%)623.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.49 V (0.24%)207.5 V0.81 V (0.39%)467.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 40 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 40 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.24V (0.12%) and delivers 207.8V at the load.

What size aluminum wire is required for 550 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.81V (0.39%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.