⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.01V (0.49%)
Voltage at Load End207.7 VLoss: 0.3 V (292.1 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A149.37 V (71.81%)58.6 V246.39 V (118.46%)142292.5 WDrop/Amp High
12 AWG3.31 mm²20 A93.86 V (45.13%)114.1 V154.83 V (74.44%)89416.4 WDrop/Amp High
10 AWG5.26 mm²30 A59.07 V (28.4%)148.9 V97.43 V (46.84%)56267.8 WDrop/Amp High
8 AWG8.37 mm²50 A37.12 V (17.85%)170.9 V61.23 V (29.44%)35360.6 WDrop/Amp High
6 AWG13.3 mm²65 A23.36 V (11.23%)184.6 V38.53 V (18.53%)22253.3 WDrop/Amp High
4 AWG21.15 mm²85 A14.69 V (7.06%)193.3 V24.23 V (11.65%)13993.8 WDrop/Amp High
3 AWG26.67 mm²100 A11.65 V (5.6%)196.4 V19.22 V (9.24%)11097.4 WDrop/Amp High
2 AWG33.62 mm²115 A9.24 V (4.44%)198.8 V15.24 V (7.33%)8803.3 WDrop/Amp High
1 AWG42.41 mm²130 A7.33 V (3.52%)200.7 V12.08 V (5.81%)6978.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.81 V (2.79%)202.2 V9.58 V (4.61%)5533.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.61 V (2.22%)203.4 V7.6 V (3.65%)4389.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.65 V (1.76%)204.3 V6.03 V (2.9%)3481.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.9 V (1.39%)205.1 V4.78 V (2.3%)2760.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.45 V (1.18%)205.5 V4.04 V (1.94%)2336.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.04 V (0.98%)206.0 V3.37 V (1.62%)1947.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.75 V (0.84%)206.2 V2.89 V (1.39%)1669.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.53 V (0.74%)206.5 V2.53 V (1.22%)1460.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.23 V (0.59%)206.8 V2.02 V (0.97%)1168.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.02 V (0.49%)207.0 V1.69 V (0.81%)973.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.82 V (0.39%)207.2 V1.35 V (0.65%)778.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.61 V (0.29%)207.4 V1.01 V (0.49%)584.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 50 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (0.14%) and delivers 207.7V at the load.

What size aluminum wire is required for 550 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.01V (0.49%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.