🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.61V (0.29%)
Voltage at Load End207.8 VLoss: 0.18 V (175.2 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A89.62 V (43.09%)118.4 V147.83 V (71.07%)85375.5 WDrop/Amp High
12 AWG3.31 mm²20 A56.32 V (27.08%)151.7 V92.9 V (44.66%)53649.9 WDrop/Amp High
10 AWG5.26 mm²30 A35.44 V (17.04%)172.6 V58.46 V (28.11%)33760.7 WDrop/Amp High
8 AWG8.37 mm²50 A22.27 V (10.71%)185.7 V36.74 V (17.66%)21216.4 WDrop/Amp High
6 AWG13.3 mm²65 A14.02 V (6.74%)194.0 V23.12 V (11.12%)13352.0 WDrop/Amp High
4 AWG21.15 mm²85 A8.81 V (4.24%)199.2 V14.54 V (6.99%)8396.3 WDrop/Amp High
3 AWG26.67 mm²100 A6.99 V (3.36%)201.0 V11.53 V (5.54%)6658.5 WDrop/Amp High
2 AWG33.62 mm²115 A5.54 V (2.67%)202.5 V9.15 V (4.4%)5282.0 WDrop/Amp High
1 AWG42.41 mm²130 A4.4 V (2.11%)203.6 V7.25 V (3.49%)4187.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.48 V (1.68%)204.5 V5.75 V (2.76%)3319.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.76 V (1.33%)205.2 V4.56 V (2.19%)2633.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.19 V (1.05%)205.8 V3.62 V (1.74%)2088.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.74 V (0.84%)206.3 V2.87 V (1.38%)1656.5 WDrop/Amp High
250 kcmil126.7 mm²255 A1.47 V (0.71%)206.5 V2.43 V (1.17%)1401.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.23 V (0.59%)206.8 V2.02 V (0.97%)1168.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.05 V (0.51%)206.9 V1.73 V (0.83%)1001.6 WDrop/Amp High
400 kcmil202.7 mm²335 A0.92 V (0.44%)207.1 V1.52 V (0.73%)876.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.74 V (0.35%)207.3 V1.21 V (0.58%)700.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.61 V (0.29%)207.4 V1.01 V (0.49%)584.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.49 V (0.24%)207.5 V0.81 V (0.39%)467.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.37 V (0.18%)207.6 V0.61 V (0.29%)350.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 30 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.18V (0.09%) and delivers 207.8V at the load.

What size aluminum wire is required for 550 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.61V (0.29%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.