⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 500 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.68V (9.73%)
Voltage at Load End116.5 VLoss: 3.54 V (1947.0 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 500 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1724.76 V (1437.3%)0.0 V2845.04 V (2370.87%)948616.7 WDrop/Amp High
12 AWG3.31 mm²20 A1083.84 V (903.2%)0.0 V1787.82 V (1489.85%)596109.6 WDrop/Amp High
10 AWG5.26 mm²30 A682.03 V (568.36%)0.0 V1125.04 V (937.53%)375118.4 WDrop/Amp High
8 AWG8.37 mm²50 A428.61 V (357.18%)0.0 V707.01 V (589.18%)235737.5 WDrop/Amp High
6 AWG13.3 mm²65 A269.74 V (224.78%)0.0 V444.94 V (370.78%)148355.1 WDrop/Amp High
4 AWG21.15 mm²85 A169.62 V (141.35%)0.0 V279.8 V (233.16%)93291.9 WDrop/Amp High
3 AWG26.67 mm²100 A134.51 V (112.1%)0.0 V221.89 V (184.9%)73982.9 WDrop/Amp High
2 AWG33.62 mm²115 A106.71 V (88.92%)13.3 V176.02 V (146.68%)58689.0 WDrop/Amp High
1 AWG42.41 mm²130 A84.59 V (70.49%)35.4 V139.54 V (116.28%)46524.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A67.07 V (55.89%)52.9 V110.63 V (92.19%)36887.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A53.2 V (44.34%)66.8 V87.76 V (73.13%)29261.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A42.2 V (35.17%)77.8 V69.61 V (58.01%)23210.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A33.47 V (27.89%)86.5 V55.2 V (46.0%)18406.0 WDrop/Amp High
250 kcmil126.7 mm²255 A28.31 V (23.6%)91.7 V46.71 V (38.92%)15573.2 WDrop/Amp High
300 kcmil152.0 mm²285 A23.6 V (19.67%)96.4 V38.93 V (32.44%)12981.1 WDrop/Amp High
350 kcmil177.3 mm²310 A20.23 V (16.86%)99.8 V33.38 V (27.81%)11128.7 WDrop/Amp High
400 kcmil202.7 mm²335 A17.7 V (14.75%)102.3 V29.19 V (24.33%)9734.2 WDrop/Amp High
500 kcmil253.4 mm²380 A14.16 V (11.8%)105.8 V23.35 V (19.46%)7786.6 WDrop/Amp High
600 kcmil304.0 mm²420 A11.8 V (9.83%)108.2 V19.47 V (16.22%)6490.5 WDrop/Amp High
750 kcmil380.0 mm²475 A9.44 V (7.87%)110.6 V15.57 V (12.98%)5192.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.08 V (5.9%)112.9 V11.68 V (9.73%)3894.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 500 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 500 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.54V (2.95%) and delivers 116.5V at the load.

What size aluminum wire is required for 550 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.68V (9.73%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.