🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 500 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.64%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 10.11V (2.11%)
Voltage at Load End476.9 VLoss: 3.06 V (2920.6 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 500 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1493.68 V (311.18%)0.0 V2463.88 V (513.31%)1422925.1 WDrop/Amp High
12 AWG3.31 mm²20 A938.63 V (195.55%)0.0 V1548.3 V (322.56%)894164.4 WDrop/Amp High
10 AWG5.26 mm²30 A590.66 V (123.05%)0.0 V974.31 V (202.98%)562677.6 WDrop/Amp High
8 AWG8.37 mm²50 A371.19 V (77.33%)108.8 V612.29 V (127.56%)353606.2 WDrop/Amp High
6 AWG13.3 mm²65 A233.6 V (48.67%)246.4 V385.33 V (80.28%)222532.6 WDrop/Amp High
4 AWG21.15 mm²85 A146.9 V (30.6%)333.1 V242.31 V (50.48%)139937.8 WDrop/Amp High
3 AWG26.67 mm²100 A116.49 V (24.27%)363.5 V192.16 V (40.03%)110974.3 WDrop/Amp High
2 AWG33.62 mm²115 A92.41 V (19.25%)387.6 V152.44 V (31.76%)88033.4 WDrop/Amp High
1 AWG42.41 mm²130 A73.26 V (15.26%)406.7 V120.84 V (25.18%)69787.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A58.08 V (12.1%)421.9 V95.81 V (19.96%)55331.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A46.08 V (9.6%)433.9 V76.0 V (15.83%)43892.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A36.55 V (7.61%)443.5 V60.29 V (12.56%)34815.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A28.98 V (6.04%)451.0 V47.81 V (9.96%)27609.0 WDrop/Amp High
250 kcmil126.7 mm²255 A24.52 V (5.11%)455.5 V40.45 V (8.43%)23359.8 WDrop/Amp High
300 kcmil152.0 mm²285 A20.44 V (4.26%)459.6 V33.72 V (7.02%)19471.6 WDrop/Amp High
350 kcmil177.3 mm²310 A17.52 V (3.65%)462.5 V28.91 V (6.02%)16693.1 WDrop/Amp High
400 kcmil202.7 mm²335 A15.33 V (3.19%)464.7 V25.28 V (5.27%)14601.3 WDrop/Amp High
500 kcmil253.4 mm²380 A12.26 V (2.55%)467.7 V20.22 V (4.21%)11679.9 WDrop/Amp High
600 kcmil304.0 mm²420 A10.22 V (2.13%)469.8 V16.86 V (3.51%)9735.8 WDrop/Amp High
750 kcmil380.0 mm²475 A8.18 V (1.7%)471.8 V13.49 V (2.81%)7788.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A6.13 V (1.28%)473.9 V10.11 V (2.11%)5841.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 500 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 500 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.06V (0.64%) and delivers 476.9V at the load.

What size aluminum wire is required for 550 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 10.11V (2.11%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.