🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.17V (7.29%)
Voltage at Load End203.4 VLoss: 4.6 V (4380.8 W)
Power & Breaker (125%)198.15 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2240.53 V (1077.18%)0.0 V3695.82 V (1776.84%)2134387.6 WDrop/Amp High
12 AWG3.31 mm²20 A1407.94 V (676.9%)0.0 V2322.45 V (1116.56%)1341246.6 WDrop/Amp High
10 AWG5.26 mm²30 A885.99 V (425.96%)0.0 V1461.47 V (702.63%)844016.4 WDrop/Amp High
8 AWG8.37 mm²50 A556.79 V (267.69%)0.0 V918.44 V (441.56%)530409.4 WDrop/Amp High
6 AWG13.3 mm²65 A350.4 V (168.46%)0.0 V577.99 V (277.88%)333799.0 WDrop/Amp High
4 AWG21.15 mm²85 A220.34 V (105.94%)0.0 V363.47 V (174.74%)209906.7 WDrop/Amp High
3 AWG26.67 mm²100 A174.74 V (84.01%)33.3 V288.24 V (138.58%)166461.4 WDrop/Amp High
2 AWG33.62 mm²115 A138.62 V (66.64%)69.4 V228.65 V (109.93%)132050.2 WDrop/Amp High
1 AWG42.41 mm²130 A109.89 V (52.83%)98.1 V181.26 V (87.15%)104681.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A87.12 V (41.89%)120.9 V143.71 V (69.09%)82997.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A69.11 V (33.23%)138.9 V114.0 V (54.81%)65839.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A54.82 V (26.36%)153.2 V90.43 V (43.48%)52223.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A43.47 V (20.9%)164.5 V71.71 V (34.48%)41413.5 WDrop/Amp High
250 kcmil126.7 mm²255 A36.78 V (17.68%)171.2 V60.67 V (29.17%)35039.7 WDrop/Amp High
300 kcmil152.0 mm²285 A30.66 V (14.74%)177.3 V50.57 V (24.31%)29207.4 WDrop/Amp High
350 kcmil177.3 mm²310 A26.28 V (12.64%)181.7 V43.36 V (20.85%)25039.6 WDrop/Amp High
400 kcmil202.7 mm²335 A22.99 V (11.05%)185.0 V37.92 V (18.23%)21902.0 WDrop/Amp High
500 kcmil253.4 mm²380 A18.39 V (8.84%)189.6 V30.34 V (14.58%)17519.8 WDrop/Amp High
600 kcmil304.0 mm²420 A15.33 V (7.37%)192.7 V25.29 V (12.16%)14603.7 WDrop/Amp High
750 kcmil380.0 mm²475 A12.26 V (5.9%)195.7 V20.23 V (9.73%)11683.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.2 V (4.42%)198.8 V15.17 V (7.29%)8761.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 750 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.6V (2.21%) and delivers 203.4V at the load.

What size aluminum wire is required for 550 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.17V (7.29%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.