🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 800 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)32× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 18.69V (155.72%)
Voltage at Load End11.7 VLoss: 0.35 V (194.7 W)
Power & Breaker (125%)6.6 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 800 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2759.61 V (22996.77%)0.0 V4552.07 V (37933.92%)1517786.8 WDrop/Amp High
12 AWG3.31 mm²20 A1734.14 V (14451.14%)0.0 V2860.52 V (23837.63%)953775.4 WDrop/Amp High
10 AWG5.26 mm²30 A1091.25 V (9093.78%)0.0 V1800.06 V (15000.49%)600189.4 WDrop/Amp High
8 AWG8.37 mm²50 A685.78 V (5714.85%)0.0 V1131.22 V (9426.83%)377180.0 WDrop/Amp High
6 AWG13.3 mm²65 A431.58 V (3596.49%)0.0 V711.9 V (5932.52%)237368.2 WDrop/Amp High
4 AWG21.15 mm²85 A271.39 V (2261.62%)0.0 V447.67 V (3730.62%)149267.0 WDrop/Amp High
3 AWG26.67 mm²100 A215.22 V (1793.52%)0.0 V355.02 V (2958.48%)118372.6 WDrop/Amp High
2 AWG33.62 mm²115 A170.73 V (1422.76%)0.0 V281.63 V (2346.89%)93902.3 WDrop/Amp High
1 AWG42.41 mm²130 A135.35 V (1127.88%)0.0 V223.26 V (1860.47%)74439.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A107.31 V (894.25%)0.0 V177.01 V (1475.09%)59020.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A85.13 V (709.38%)0.0 V140.42 V (1170.14%)46818.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A67.52 V (562.68%)0.0 V111.38 V (928.16%)37136.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A53.54 V (446.21%)0.0 V88.32 V (736.03%)29449.6 WDrop/Amp High
250 kcmil126.7 mm²255 A45.3 V (377.53%)0.0 V74.73 V (622.75%)24917.1 WDrop/Amp High
300 kcmil152.0 mm²285 A37.76 V (314.69%)0.0 V62.29 V (519.1%)20769.7 WDrop/Amp High
350 kcmil177.3 mm²310 A32.37 V (269.79%)0.0 V53.4 V (445.02%)17806.0 WDrop/Amp High
400 kcmil202.7 mm²335 A28.32 V (235.98%)0.0 V46.71 V (389.26%)15574.7 WDrop/Amp High
500 kcmil253.4 mm²380 A22.65 V (188.77%)0.0 V37.37 V (311.38%)12458.5 WDrop/Amp High
600 kcmil304.0 mm²420 A18.88 V (157.35%)0.0 V31.15 V (259.55%)10384.9 WDrop/Amp High
750 kcmil380.0 mm²475 A15.11 V (125.88%)0.0 V24.92 V (207.64%)8307.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.33 V (94.4%)0.7 V18.69 V (155.72%)6230.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 800 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 800 feet one-way at 12V (DC), you need 32× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 550 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 18.69V (155.72%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.