⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 100 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.21V (0.92%)
Voltage at Load End239.3 VLoss: 0.67 V (695.1 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A325.89 V (135.79%)0.0 V537.57 V (223.99%)338679.7 WDrop/Amp High
12 AWG3.31 mm²20 A204.79 V (85.33%)35.2 V337.81 V (140.75%)212825.9 WDrop/Amp High
10 AWG5.26 mm²30 A128.87 V (53.7%)111.1 V212.58 V (88.57%)133926.6 WDrop/Amp High
8 AWG8.37 mm²50 A80.99 V (33.74%)159.0 V133.59 V (55.66%)84164.1 WDrop/Amp High
6 AWG13.3 mm²65 A50.97 V (21.24%)189.0 V84.07 V (35.03%)52966.4 WDrop/Amp High
4 AWG21.15 mm²85 A32.05 V (13.35%)207.9 V52.87 V (22.03%)33307.5 WDrop/Amp High
3 AWG26.67 mm²100 A25.42 V (10.59%)214.6 V41.93 V (17.47%)26413.7 WDrop/Amp High
2 AWG33.62 mm²115 A20.16 V (8.4%)219.8 V33.26 V (13.86%)20953.4 WDrop/Amp High
1 AWG42.41 mm²130 A15.98 V (6.66%)224.0 V26.37 V (10.99%)16610.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.67 V (5.28%)227.3 V20.9 V (8.71%)13169.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.05 V (4.19%)229.9 V16.58 V (6.91%)10447.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.97 V (3.32%)232.0 V13.15 V (5.48%)8286.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.32 V (2.63%)233.7 V10.43 V (4.35%)6571.4 WDrop/Amp High
250 kcmil126.7 mm²255 A5.35 V (2.23%)234.6 V8.83 V (3.68%)5560.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.46 V (1.86%)235.5 V7.36 V (3.07%)4634.6 WDrop/Amp High
350 kcmil177.3 mm²310 A3.82 V (1.59%)236.2 V6.31 V (2.63%)3973.2 WDrop/Amp High
400 kcmil202.7 mm²335 A3.34 V (1.39%)236.7 V5.52 V (2.3%)3475.4 WDrop/Amp High
500 kcmil253.4 mm²380 A2.68 V (1.11%)237.3 V4.41 V (1.84%)2780.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.23 V (0.93%)237.8 V3.68 V (1.53%)2317.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.78 V (0.74%)238.2 V2.94 V (1.23%)1853.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.34 V (0.56%)238.7 V2.21 V (0.92%)1390.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 100 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.67V (0.28%) and delivers 239.3V at the load.

What size aluminum wire is required for 600 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.21V (0.92%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.