⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 75 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.66V (0.69%)
Voltage at Load End239.5 VLoss: 0.5 V (521.4 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A244.42 V (101.84%)0.0 V403.18 V (167.99%)254009.8 WDrop/Amp High
12 AWG3.31 mm²20 A153.59 V (64.0%)86.4 V253.36 V (105.57%)159619.4 WDrop/Amp High
10 AWG5.26 mm²30 A96.65 V (40.27%)143.3 V159.43 V (66.43%)100444.9 WDrop/Amp High
8 AWG8.37 mm²50 A60.74 V (25.31%)179.3 V100.19 V (41.75%)63123.1 WDrop/Amp High
6 AWG13.3 mm²65 A38.23 V (15.93%)201.8 V63.05 V (26.27%)39724.8 WDrop/Amp High
4 AWG21.15 mm²85 A24.04 V (10.02%)216.0 V39.65 V (16.52%)24980.6 WDrop/Amp High
3 AWG26.67 mm²100 A19.06 V (7.94%)220.9 V31.44 V (13.1%)19810.3 WDrop/Amp High
2 AWG33.62 mm²115 A15.12 V (6.3%)224.9 V24.94 V (10.39%)15715.1 WDrop/Amp High
1 AWG42.41 mm²130 A11.99 V (4.99%)228.0 V19.77 V (8.24%)12457.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.5 V (3.96%)230.5 V15.68 V (6.53%)9877.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.54 V (3.14%)232.5 V12.44 V (5.18%)7835.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.98 V (2.49%)234.0 V9.86 V (4.11%)6215.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.74 V (1.98%)235.3 V7.82 V (3.26%)4928.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.01 V (1.67%)236.0 V6.62 V (2.76%)4170.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.34 V (1.39%)236.7 V5.52 V (2.3%)3475.9 WDrop/Amp High
350 kcmil177.3 mm²310 A2.87 V (1.19%)237.1 V4.73 V (1.97%)2979.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.51 V (1.05%)237.5 V4.14 V (1.72%)2606.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.01 V (0.84%)238.0 V3.31 V (1.38%)2085.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.67 V (0.7%)238.3 V2.76 V (1.15%)1738.0 WDrop/Amp High
750 kcmil380.0 mm²475 A1.34 V (0.56%)238.7 V2.21 V (0.92%)1390.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.0 V (0.42%)239.0 V1.66 V (0.69%)1042.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 75 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.5V (0.21%) and delivers 239.5V at the load.

What size aluminum wire is required for 600 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.66V (0.69%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.