⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.66V (0.28%)
Voltage at Load End239.8 VLoss: 0.2 V (208.6 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A97.77 V (40.74%)142.2 V161.27 V (67.2%)101603.9 WDrop/Amp High
12 AWG3.31 mm²20 A61.44 V (25.6%)178.6 V101.34 V (42.23%)63847.8 WDrop/Amp High
10 AWG5.26 mm²30 A38.66 V (16.11%)201.3 V63.77 V (26.57%)40178.0 WDrop/Amp High
8 AWG8.37 mm²50 A24.3 V (10.12%)215.7 V40.08 V (16.7%)25249.2 WDrop/Amp High
6 AWG13.3 mm²65 A15.29 V (6.37%)224.7 V25.22 V (10.51%)15889.9 WDrop/Amp High
4 AWG21.15 mm²85 A9.62 V (4.01%)230.4 V15.86 V (6.61%)9992.3 WDrop/Amp High
3 AWG26.67 mm²100 A7.62 V (3.18%)232.4 V12.58 V (5.24%)7924.1 WDrop/Amp High
2 AWG33.62 mm²115 A6.05 V (2.52%)234.0 V9.98 V (4.16%)6286.0 WDrop/Amp High
1 AWG42.41 mm²130 A4.8 V (2.0%)235.2 V7.91 V (3.3%)4983.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.8 V (1.58%)236.2 V6.27 V (2.61%)3950.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.02 V (1.26%)237.0 V4.97 V (2.07%)3134.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.39 V (1.0%)237.6 V3.95 V (1.64%)2486.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.9 V (0.79%)238.1 V3.13 V (1.3%)1971.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.61 V (0.67%)238.4 V2.65 V (1.1%)1668.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.34 V (0.56%)238.7 V2.21 V (0.92%)1390.4 WDrop/Amp High
350 kcmil177.3 mm²310 A1.15 V (0.48%)238.9 V1.89 V (0.79%)1192.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.0 V (0.42%)239.0 V1.65 V (0.69%)1042.6 WDrop/Amp High
500 kcmil253.4 mm²380 A0.8 V (0.33%)239.2 V1.32 V (0.55%)834.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.67 V (0.28%)239.3 V1.1 V (0.46%)695.2 WDrop/Amp High
750 kcmil380.0 mm²475 A0.54 V (0.22%)239.5 V0.88 V (0.37%)556.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.4 V (0.17%)239.6 V0.66 V (0.28%)417.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 30 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.2V (0.09%) and delivers 239.8V at the load.

What size aluminum wire is required for 600 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.66V (0.28%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.