⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 150 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.31V (1.38%)
Voltage at Load End239.0 VLoss: 1.0 V (1042.7 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 150 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A488.84 V (203.68%)0.0 V806.36 V (335.98%)508019.5 WDrop/Amp High
12 AWG3.31 mm²20 A307.19 V (127.99%)0.0 V506.72 V (211.13%)319238.9 WDrop/Amp High
10 AWG5.26 mm²30 A193.31 V (80.54%)46.7 V318.87 V (132.86%)200889.9 WDrop/Amp High
8 AWG8.37 mm²50 A121.48 V (50.62%)118.5 V200.39 V (83.49%)126246.2 WDrop/Amp High
6 AWG13.3 mm²65 A76.45 V (31.85%)163.5 V126.11 V (52.54%)79449.7 WDrop/Amp High
4 AWG21.15 mm²85 A48.08 V (20.03%)191.9 V79.3 V (33.04%)49961.3 WDrop/Amp High
3 AWG26.67 mm²100 A38.12 V (15.89%)201.9 V62.89 V (26.2%)39620.6 WDrop/Amp High
2 AWG33.62 mm²115 A30.24 V (12.6%)209.8 V49.89 V (20.79%)31430.1 WDrop/Amp High
1 AWG42.41 mm²130 A23.98 V (9.99%)216.0 V39.55 V (16.48%)24915.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.01 V (7.92%)221.0 V31.36 V (13.06%)19754.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.08 V (6.28%)224.9 V24.87 V (10.36%)15670.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.96 V (4.98%)228.0 V19.73 V (8.22%)12430.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.48 V (3.95%)230.5 V15.65 V (6.52%)9857.1 WDrop/Amp High
250 kcmil126.7 mm²255 A8.03 V (3.34%)232.0 V13.24 V (5.52%)8340.0 WDrop/Amp High
300 kcmil152.0 mm²285 A6.69 V (2.79%)233.3 V11.03 V (4.6%)6951.8 WDrop/Amp High
350 kcmil177.3 mm²310 A5.73 V (2.39%)234.3 V9.46 V (3.94%)5959.8 WDrop/Amp High
400 kcmil202.7 mm²335 A5.02 V (2.09%)235.0 V8.27 V (3.45%)5213.0 WDrop/Amp High
500 kcmil253.4 mm²380 A4.01 V (1.67%)236.0 V6.62 V (2.76%)4170.0 WDrop/Amp High
600 kcmil304.0 mm²420 A3.34 V (1.39%)236.7 V5.52 V (2.3%)3475.9 WDrop/Amp High
750 kcmil380.0 mm²475 A2.68 V (1.11%)237.3 V4.41 V (1.84%)2780.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.01 V (0.84%)238.0 V3.31 V (1.38%)2085.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 150 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 150 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.0V (0.42%) and delivers 239.0V at the load.

What size aluminum wire is required for 600 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.31V (1.38%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.