🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 60 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.32V (0.55%)
Voltage at Load End239.6 VLoss: 0.4 V (417.1 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A195.54 V (81.47%)44.5 V322.54 V (134.39%)203207.8 WDrop/Amp High
12 AWG3.31 mm²20 A122.88 V (51.2%)117.1 V202.69 V (84.45%)127695.5 WDrop/Amp High
10 AWG5.26 mm²30 A77.32 V (32.22%)162.7 V127.55 V (53.14%)80355.9 WDrop/Amp High
8 AWG8.37 mm²50 A48.59 V (20.25%)191.4 V80.15 V (33.4%)50498.5 WDrop/Amp High
6 AWG13.3 mm²65 A30.58 V (12.74%)209.4 V50.44 V (21.02%)31779.9 WDrop/Amp High
4 AWG21.15 mm²85 A19.23 V (8.01%)220.8 V31.72 V (13.22%)19984.5 WDrop/Amp High
3 AWG26.67 mm²100 A15.25 V (6.35%)224.8 V25.16 V (10.48%)15848.2 WDrop/Amp High
2 AWG33.62 mm²115 A12.1 V (5.04%)227.9 V19.96 V (8.31%)12572.0 WDrop/Amp High
1 AWG42.41 mm²130 A9.59 V (4.0%)230.4 V15.82 V (6.59%)9966.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.6 V (3.17%)232.4 V12.54 V (5.23%)7901.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.03 V (2.51%)234.0 V9.95 V (4.15%)6268.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.78 V (1.99%)235.2 V7.89 V (3.29%)4972.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.79 V (1.58%)236.2 V6.26 V (2.61%)3942.8 WDrop/Amp High
250 kcmil126.7 mm²255 A3.21 V (1.34%)236.8 V5.3 V (2.21%)3336.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.68 V (1.11%)237.3 V4.41 V (1.84%)2780.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.29 V (0.96%)237.7 V3.78 V (1.58%)2383.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.01 V (0.84%)238.0 V3.31 V (1.38%)2085.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.61 V (0.67%)238.4 V2.65 V (1.1%)1668.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.34 V (0.56%)238.7 V2.21 V (0.92%)1390.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.07 V (0.45%)238.9 V1.77 V (0.74%)1112.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.8 V (0.33%)239.2 V1.32 V (0.55%)834.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 60 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.4V (0.17%) and delivers 239.6V at the load.

What size aluminum wire is required for 600 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.32V (0.55%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.