🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.29V (12.74%)
Voltage at Load End116.9 VLoss: 3.09 V (1853.7 W)
Power & Breaker (125%)72.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2257.86 V (1881.55%)0.0 V3724.42 V (3103.68%)1354718.8 WDrop/Amp High
12 AWG3.31 mm²20 A1418.84 V (1182.37%)0.0 V2340.42 V (1950.35%)851303.6 WDrop/Amp High
10 AWG5.26 mm²30 A892.84 V (744.04%)0.0 V1472.78 V (1227.31%)535706.3 WDrop/Amp High
8 AWG8.37 mm²50 A561.09 V (467.58%)0.0 V925.54 V (771.29%)336656.5 WDrop/Amp High
6 AWG13.3 mm²65 A353.11 V (294.26%)0.0 V582.47 V (485.39%)211865.8 WDrop/Amp High
4 AWG21.15 mm²85 A222.05 V (185.04%)0.0 V366.28 V (305.23%)133230.0 WDrop/Amp High
3 AWG26.67 mm²100 A176.09 V (146.74%)0.0 V290.47 V (242.06%)105654.9 WDrop/Amp High
2 AWG33.62 mm²115 A139.69 V (116.41%)0.0 V230.42 V (192.02%)83813.7 WDrop/Amp High
1 AWG42.41 mm²130 A110.74 V (92.28%)9.3 V182.66 V (152.22%)66442.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A87.8 V (73.17%)32.2 V144.83 V (120.69%)52679.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A69.65 V (58.04%)50.4 V114.89 V (95.74%)41788.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A55.24 V (46.04%)64.8 V91.13 V (75.94%)33146.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A43.81 V (36.51%)76.2 V72.26 V (60.22%)26285.6 WDrop/Amp High
250 kcmil126.7 mm²255 A37.07 V (30.89%)82.9 V61.14 V (50.95%)22240.1 WDrop/Amp High
300 kcmil152.0 mm²285 A30.9 V (25.75%)89.1 V50.97 V (42.47%)18538.3 WDrop/Amp High
350 kcmil177.3 mm²310 A26.49 V (22.07%)93.5 V43.69 V (36.41%)15892.9 WDrop/Amp High
400 kcmil202.7 mm²335 A23.17 V (19.31%)96.8 V38.22 V (31.85%)13901.4 WDrop/Amp High
500 kcmil253.4 mm²380 A18.53 V (15.44%)101.5 V30.57 V (25.48%)11120.0 WDrop/Amp High
600 kcmil304.0 mm²420 A15.45 V (12.87%)104.6 V25.48 V (21.24%)9269.1 WDrop/Amp High
750 kcmil380.0 mm²475 A12.36 V (10.3%)107.6 V20.39 V (16.99%)7415.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.27 V (7.72%)110.7 V15.29 V (12.74%)5561.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 600 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.09V (2.57%) and delivers 116.9V at the load.

What size aluminum wire is required for 600 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.29V (12.74%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.