650 Amp Wire Size at 125 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.43%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.99V (1.44%)
Voltage at Load End207.1 VLoss: 0.91 V (1019.8 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 125 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A441.32 V (212.17%)0.0 V727.96 V (349.98%)496847.8 WDrop/Amp High
12 AWG3.31 mm²20 A277.32 V (133.33%)0.0 V457.45 V (219.93%)312218.6 WDrop/Amp High
10 AWG5.26 mm²30 A174.51 V (83.9%)33.5 V287.86 V (138.4%)196472.1 WDrop/Amp High
8 AWG8.37 mm²50 A109.67 V (52.73%)98.3 V180.9 V (86.97%)123469.9 WDrop/Amp High
6 AWG13.3 mm²65 A69.02 V (33.18%)139.0 V113.85 V (54.73%)77702.5 WDrop/Amp High
4 AWG21.15 mm²85 A43.4 V (20.87%)164.6 V71.59 V (34.42%)48862.6 WDrop/Amp High
3 AWG26.67 mm²100 A34.42 V (16.55%)173.6 V56.77 V (27.3%)38749.3 WDrop/Amp High
2 AWG33.62 mm²115 A27.3 V (13.13%)180.7 V45.04 V (21.65%)30738.9 WDrop/Amp High
1 AWG42.41 mm²130 A21.64 V (10.41%)186.4 V35.7 V (17.16%)24367.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.16 V (8.25%)190.8 V28.31 V (13.61%)19320.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.61 V (6.54%)194.4 V22.46 V (10.8%)15326.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.8 V (5.19%)197.2 V17.81 V (8.56%)12156.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.56 V (4.12%)199.4 V14.12 V (6.79%)9640.3 WDrop/Amp High
250 kcmil126.7 mm²255 A7.24 V (3.48%)200.8 V11.95 V (5.75%)8156.6 WDrop/Amp High
300 kcmil152.0 mm²285 A6.04 V (2.9%)202.0 V9.96 V (4.79%)6799.0 WDrop/Amp High
350 kcmil177.3 mm²310 A5.18 V (2.49%)202.8 V8.54 V (4.11%)5828.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.53 V (2.18%)203.5 V7.47 V (3.59%)5098.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.62 V (1.74%)204.4 V5.98 V (2.87%)4078.3 WDrop/Amp High
600 kcmil304.0 mm²420 A3.02 V (1.45%)205.0 V4.98 V (2.39%)3399.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.42 V (1.16%)205.6 V3.98 V (1.92%)2719.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.81 V (0.87%)206.2 V2.99 V (1.44%)2039.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 125 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 125 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.91V (0.43%) and delivers 207.1V at the load.

What size aluminum wire is required for 650 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.99V (1.44%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.