🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 40 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.96V (0.46%)
Voltage at Load End207.7 VLoss: 0.29 V (326.4 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 40 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A141.22 V (67.89%)66.8 V232.95 V (111.99%)158991.3 WDrop/Amp High
12 AWG3.31 mm²20 A88.74 V (42.66%)119.3 V146.38 V (70.38%)99909.9 WDrop/Amp High
10 AWG5.26 mm²30 A55.84 V (26.85%)152.2 V92.12 V (44.29%)62871.1 WDrop/Amp High
8 AWG8.37 mm²50 A35.09 V (16.87%)172.9 V57.89 V (27.83%)39510.4 WDrop/Amp High
6 AWG13.3 mm²65 A22.09 V (10.62%)185.9 V36.43 V (17.51%)24864.8 WDrop/Amp High
4 AWG21.15 mm²85 A13.89 V (6.68%)194.1 V22.91 V (11.01%)15636.0 WDrop/Amp High
3 AWG26.67 mm²100 A11.01 V (5.3%)197.0 V18.17 V (8.73%)12399.8 WDrop/Amp High
2 AWG33.62 mm²115 A8.74 V (4.2%)199.3 V14.41 V (6.93%)9836.5 WDrop/Amp High
1 AWG42.41 mm²130 A6.93 V (3.33%)201.1 V11.42 V (5.49%)7797.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.49 V (2.64%)202.5 V9.06 V (4.35%)6182.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.36 V (2.09%)203.6 V7.19 V (3.45%)4904.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.46 V (1.66%)204.5 V5.7 V (2.74%)3890.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.74 V (1.32%)205.3 V4.52 V (2.17%)3084.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.32 V (1.11%)205.7 V3.82 V (1.84%)2610.1 WDrop/Amp High
300 kcmil152.0 mm²285 A1.93 V (0.93%)206.1 V3.19 V (1.53%)2175.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.66 V (0.8%)206.3 V2.73 V (1.31%)1865.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.45 V (0.7%)206.6 V2.39 V (1.15%)1631.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.16 V (0.56%)206.8 V1.91 V (0.92%)1305.1 WDrop/Amp High
600 kcmil304.0 mm²420 A0.97 V (0.46%)207.0 V1.59 V (0.77%)1087.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.77 V (0.37%)207.2 V1.28 V (0.61%)870.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.58 V (0.28%)207.4 V0.96 V (0.46%)652.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 40 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 40 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (0.14%) and delivers 207.7V at the load.

What size aluminum wire is required for 650 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.96V (0.46%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.