🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 20 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.07%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.48V (0.23%)
Voltage at Load End207.9 VLoss: 0.14 V (163.2 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 20 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A70.61 V (33.95%)137.4 V116.47 V (56.0%)79495.6 WDrop/Amp High
12 AWG3.31 mm²20 A44.37 V (21.33%)163.6 V73.19 V (35.19%)49955.0 WDrop/Amp High
10 AWG5.26 mm²30 A27.92 V (13.42%)180.1 V46.06 V (22.14%)31435.5 WDrop/Amp High
8 AWG8.37 mm²50 A17.55 V (8.44%)190.5 V28.94 V (13.92%)19755.2 WDrop/Amp High
6 AWG13.3 mm²65 A11.04 V (5.31%)197.0 V18.22 V (8.76%)12432.4 WDrop/Amp High
4 AWG21.15 mm²85 A6.94 V (3.34%)201.1 V11.45 V (5.51%)7818.0 WDrop/Amp High
3 AWG26.67 mm²100 A5.51 V (2.65%)202.5 V9.08 V (4.37%)6199.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.37 V (2.1%)203.6 V7.21 V (3.46%)4918.2 WDrop/Amp High
1 AWG42.41 mm²130 A3.46 V (1.66%)204.5 V5.71 V (2.75%)3898.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.75 V (1.32%)205.3 V4.53 V (2.18%)3091.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.18 V (1.05%)205.8 V3.59 V (1.73%)2452.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.73 V (0.83%)206.3 V2.85 V (1.37%)1945.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.37 V (0.66%)206.6 V2.26 V (1.09%)1542.5 WDrop/Amp High
250 kcmil126.7 mm²255 A1.16 V (0.56%)206.8 V1.91 V (0.92%)1305.1 WDrop/Amp High
300 kcmil152.0 mm²285 A0.97 V (0.46%)207.0 V1.59 V (0.77%)1087.8 WDrop/Amp High
350 kcmil177.3 mm²310 A0.83 V (0.4%)207.2 V1.37 V (0.66%)932.6 WDrop/Amp High
400 kcmil202.7 mm²335 A0.72 V (0.35%)207.3 V1.2 V (0.57%)815.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.58 V (0.28%)207.4 V0.96 V (0.46%)652.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.48 V (0.23%)207.5 V0.8 V (0.38%)543.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.39 V (0.19%)207.6 V0.64 V (0.31%)435.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.29 V (0.14%)207.7 V0.48 V (0.23%)326.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 20 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 20 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.14V (0.07%) and delivers 207.9V at the load.

What size aluminum wire is required for 650 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.48V (0.23%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.