🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.91V (0.92%)
Voltage at Load End207.4 VLoss: 0.58 V (652.6 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A282.44 V (135.79%)0.0 V465.9 V (223.99%)317982.6 WDrop/Amp High
12 AWG3.31 mm²20 A177.49 V (85.33%)30.5 V292.77 V (140.75%)199819.9 WDrop/Amp High
10 AWG5.26 mm²30 A111.69 V (53.7%)96.3 V184.23 V (88.57%)125742.2 WDrop/Amp High
8 AWG8.37 mm²50 A70.19 V (33.74%)137.8 V115.78 V (55.66%)79020.8 WDrop/Amp High
6 AWG13.3 mm²65 A44.17 V (21.24%)163.8 V72.86 V (35.03%)49729.6 WDrop/Amp High
4 AWG21.15 mm²85 A27.78 V (13.35%)180.2 V45.82 V (22.03%)31272.0 WDrop/Amp High
3 AWG26.67 mm²100 A22.03 V (10.59%)186.0 V36.34 V (17.47%)24799.5 WDrop/Amp High
2 AWG33.62 mm²115 A17.47 V (8.4%)190.5 V28.82 V (13.86%)19672.9 WDrop/Amp High
1 AWG42.41 mm²130 A13.85 V (6.66%)194.1 V22.85 V (10.99%)15595.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.98 V (5.28%)197.0 V18.12 V (8.71%)12365.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.71 V (4.19%)199.3 V14.37 V (6.91%)9808.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.91 V (3.32%)201.1 V11.4 V (5.48%)7780.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.48 V (2.63%)202.5 V9.04 V (4.35%)6169.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.64 V (2.23%)203.4 V7.65 V (3.68%)5220.2 WDrop/Amp High
300 kcmil152.0 mm²285 A3.86 V (1.86%)204.1 V6.38 V (3.07%)4351.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.31 V (1.59%)204.7 V5.47 V (2.63%)3730.4 WDrop/Amp High
400 kcmil202.7 mm²335 A2.9 V (1.39%)205.1 V4.78 V (2.3%)3263.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.32 V (1.11%)205.7 V3.82 V (1.84%)2610.1 WDrop/Amp High
600 kcmil304.0 mm²420 A1.93 V (0.93%)206.1 V3.19 V (1.53%)2175.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.55 V (0.74%)206.5 V2.55 V (1.23%)1740.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.16 V (0.56%)206.8 V1.91 V (0.92%)1305.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 80 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.58V (0.28%) and delivers 207.4V at the load.

What size aluminum wire is required for 650 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.91V (0.92%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.