🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 200 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.52V (2.3%)
Voltage at Load End238.3 VLoss: 1.68 V (1087.8 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A815.34 V (339.72%)0.0 V1344.93 V (560.39%)529971.0 WDrop/Amp High
12 AWG3.31 mm²20 A512.36 V (213.48%)0.0 V845.15 V (352.15%)333033.1 WDrop/Amp High
10 AWG5.26 mm²30 A322.42 V (134.34%)0.0 V531.84 V (221.6%)209570.3 WDrop/Amp High
8 AWG8.37 mm²50 A202.62 V (84.42%)37.4 V334.22 V (139.26%)131701.3 WDrop/Amp High
6 AWG13.3 mm²65 A127.51 V (53.13%)112.5 V210.33 V (87.64%)82882.7 WDrop/Amp High
4 AWG21.15 mm²85 A80.18 V (33.41%)159.8 V132.27 V (55.11%)52120.1 WDrop/Amp High
3 AWG26.67 mm²100 A63.59 V (26.5%)176.4 V104.89 V (43.7%)41332.6 WDrop/Amp High
2 AWG33.62 mm²115 A50.44 V (21.02%)189.6 V83.21 V (34.67%)32788.2 WDrop/Amp High
1 AWG42.41 mm²130 A39.99 V (16.66%)200.0 V65.96 V (27.48%)25992.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.71 V (13.21%)208.3 V52.3 V (21.79%)20608.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.15 V (10.48%)214.8 V41.49 V (17.29%)16347.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.95 V (8.31%)220.1 V32.91 V (13.71%)12967.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.82 V (6.59%)224.2 V26.1 V (10.87%)10283.0 WDrop/Amp High
250 kcmil126.7 mm²255 A13.39 V (5.58%)226.6 V22.08 V (9.2%)8700.4 WDrop/Amp High
300 kcmil152.0 mm²285 A11.16 V (4.65%)228.8 V18.4 V (7.67%)7252.2 WDrop/Amp High
350 kcmil177.3 mm²310 A9.57 V (3.99%)230.4 V15.78 V (6.57%)6217.4 WDrop/Amp High
400 kcmil202.7 mm²335 A8.37 V (3.49%)231.6 V13.8 V (5.75%)5438.3 WDrop/Amp High
500 kcmil253.4 mm²380 A6.69 V (2.79%)233.3 V11.04 V (4.6%)4350.2 WDrop/Amp High
600 kcmil304.0 mm²420 A5.58 V (2.32%)234.4 V9.2 V (3.83%)3626.1 WDrop/Amp High
750 kcmil380.0 mm²475 A4.46 V (1.86%)235.5 V7.36 V (3.07%)2900.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.35 V (1.39%)236.7 V5.52 V (2.3%)2175.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 200 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.68V (0.69%) and delivers 238.3V at the load.

What size aluminum wire is required for 650 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.52V (2.3%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.