⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.21V (2.59%)
Voltage at Load End238.1 VLoss: 1.89 V (1223.8 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A917.26 V (382.19%)0.0 V1513.05 V (630.44%)596217.4 WDrop/Amp High
12 AWG3.31 mm²20 A576.4 V (240.17%)0.0 V950.8 V (396.17%)374662.3 WDrop/Amp High
10 AWG5.26 mm²30 A362.72 V (151.13%)0.0 V598.31 V (249.3%)235766.6 WDrop/Amp High
8 AWG8.37 mm²50 A227.94 V (94.98%)12.1 V376.0 V (156.67%)148163.9 WDrop/Amp High
6 AWG13.3 mm²65 A143.45 V (59.77%)96.5 V236.63 V (98.59%)93243.0 WDrop/Amp High
4 AWG21.15 mm²85 A90.21 V (37.59%)149.8 V148.8 V (62.0%)58635.1 WDrop/Amp High
3 AWG26.67 mm²100 A71.54 V (29.81%)168.5 V118.0 V (49.17%)46499.1 WDrop/Amp High
2 AWG33.62 mm²115 A56.75 V (23.65%)183.3 V93.61 V (39.0%)36886.7 WDrop/Amp High
1 AWG42.41 mm²130 A44.99 V (18.74%)195.0 V74.21 V (30.92%)29241.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A35.67 V (14.86%)204.3 V58.84 V (24.51%)23184.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A28.29 V (11.79%)211.7 V46.67 V (19.45%)18391.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.44 V (9.35%)217.6 V37.02 V (15.43%)14588.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.8 V (7.42%)222.2 V29.36 V (12.23%)11568.4 WDrop/Amp High
250 kcmil126.7 mm²255 A15.06 V (6.27%)224.9 V24.84 V (10.35%)9787.9 WDrop/Amp High
300 kcmil152.0 mm²285 A12.55 V (5.23%)227.4 V20.7 V (8.63%)8158.8 WDrop/Amp High
350 kcmil177.3 mm²310 A10.76 V (4.48%)229.2 V17.75 V (7.4%)6994.5 WDrop/Amp High
400 kcmil202.7 mm²335 A9.41 V (3.92%)230.6 V15.53 V (6.47%)6118.1 WDrop/Amp High
500 kcmil253.4 mm²380 A7.53 V (3.14%)232.5 V12.42 V (5.17%)4894.0 WDrop/Amp High
600 kcmil304.0 mm²420 A6.28 V (2.61%)233.7 V10.35 V (4.31%)4079.4 WDrop/Amp High
750 kcmil380.0 mm²475 A5.02 V (2.09%)235.0 V8.28 V (3.45%)3263.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.77 V (1.57%)236.2 V6.21 V (2.59%)2447.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 225 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.89V (0.79%) and delivers 238.1V at the load.

What size aluminum wire is required for 650 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.21V (2.59%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.