🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 350 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)17× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.87%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.66V (80.51%)
Voltage at Load End11.7 VLoss: 0.34 V (224.0 W)
Power & Breaker (125%)7.8 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 350 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1426.85 V (11890.38%)0.0 V2353.63 V (19613.56%)927449.2 WDrop/Amp High
12 AWG3.31 mm²20 A896.63 V (7471.9%)0.0 V1479.02 V (12325.14%)582808.0 WDrop/Amp High
10 AWG5.26 mm²30 A564.23 V (4701.9%)0.0 V930.71 V (7755.93%)366748.0 WDrop/Amp High
8 AWG8.37 mm²50 A354.58 V (2954.84%)0.0 V584.89 V (4874.1%)230477.2 WDrop/Amp High
6 AWG13.3 mm²65 A223.15 V (1859.55%)0.0 V368.09 V (3067.38%)145044.7 WDrop/Amp High
4 AWG21.15 mm²85 A140.32 V (1169.36%)0.0 V231.47 V (1928.9%)91210.1 WDrop/Amp High
3 AWG26.67 mm²100 A111.28 V (927.33%)0.0 V183.56 V (1529.67%)72332.0 WDrop/Amp High
2 AWG33.62 mm²115 A88.28 V (735.63%)0.0 V145.61 V (1213.45%)57379.4 WDrop/Amp High
1 AWG42.41 mm²130 A69.98 V (583.16%)0.0 V115.43 V (961.95%)45486.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A55.48 V (462.37%)0.0 V91.52 V (762.69%)36064.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A44.01 V (366.78%)0.0 V72.6 V (605.02%)28608.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.91 V (290.93%)0.0 V57.59 V (479.9%)22692.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.69 V (230.71%)0.0 V45.67 V (380.56%)17995.3 WDrop/Amp High
250 kcmil126.7 mm²255 A23.42 V (195.2%)0.0 V38.64 V (321.99%)15225.7 WDrop/Amp High
300 kcmil152.0 mm²285 A19.53 V (162.71%)0.0 V32.21 V (268.4%)12691.4 WDrop/Amp High
350 kcmil177.3 mm²310 A16.74 V (139.49%)0.0 V27.61 V (230.1%)10880.4 WDrop/Amp High
400 kcmil202.7 mm²335 A14.64 V (122.01%)0.0 V24.15 V (201.26%)9517.0 WDrop/Amp High
500 kcmil253.4 mm²380 A11.71 V (97.6%)0.3 V19.32 V (161.0%)7612.8 WDrop/Amp High
600 kcmil304.0 mm²420 A9.76 V (81.36%)2.2 V16.1 V (134.2%)6345.7 WDrop/Amp High
750 kcmil380.0 mm²475 A7.81 V (65.08%)4.2 V12.88 V (107.36%)5076.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.86 V (48.81%)6.1 V9.66 V (80.51%)3807.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 350 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 350 feet one-way at 12V (DC), you need 17× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.87%) and delivers 11.7V at the load.

What size aluminum wire is required for 650 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.66V (80.51%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.