⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.09%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.56V (6.9%)
Voltage at Load End235.0 VLoss: 5.02 V (3263.3 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2446.02 V (1019.17%)0.0 V4034.79 V (1681.16%)1589913.0 WDrop/Amp High
12 AWG3.31 mm²20 A1537.08 V (640.45%)0.0 V2535.46 V (1056.44%)999099.4 WDrop/Amp High
10 AWG5.26 mm²30 A967.25 V (403.02%)0.0 V1595.51 V (664.79%)628710.8 WDrop/Amp High
8 AWG8.37 mm²50 A607.85 V (253.27%)0.0 V1002.67 V (417.78%)395103.8 WDrop/Amp High
6 AWG13.3 mm²65 A382.54 V (159.39%)0.0 V631.0 V (262.92%)248648.0 WDrop/Amp High
4 AWG21.15 mm²85 A240.55 V (100.23%)0.0 V396.8 V (165.33%)156360.2 WDrop/Amp High
3 AWG26.67 mm²100 A190.77 V (79.49%)49.2 V314.67 V (131.11%)123997.7 WDrop/Amp High
2 AWG33.62 mm²115 A151.33 V (63.05%)88.7 V249.62 V (104.01%)98364.6 WDrop/Amp High
1 AWG42.41 mm²130 A119.97 V (49.99%)120.0 V197.89 V (82.45%)77977.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A95.12 V (39.63%)144.9 V156.9 V (65.37%)61825.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A75.45 V (31.44%)164.5 V124.46 V (51.86%)49043.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A59.85 V (24.94%)180.2 V98.72 V (41.13%)38901.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A47.46 V (19.78%)192.5 V78.29 V (32.62%)30849.1 WDrop/Amp High
250 kcmil126.7 mm²255 A40.16 V (16.73%)199.8 V66.24 V (27.6%)26101.2 WDrop/Amp High
300 kcmil152.0 mm²285 A33.47 V (13.95%)206.5 V55.21 V (23.01%)21756.7 WDrop/Amp High
350 kcmil177.3 mm²310 A28.7 V (11.96%)211.3 V47.33 V (19.72%)18652.1 WDrop/Amp High
400 kcmil202.7 mm²335 A25.1 V (10.46%)214.9 V41.4 V (17.25%)16314.8 WDrop/Amp High
500 kcmil253.4 mm²380 A20.08 V (8.37%)219.9 V33.12 V (13.8%)13050.6 WDrop/Amp High
600 kcmil304.0 mm²420 A16.74 V (6.97%)223.3 V27.61 V (11.5%)10878.4 WDrop/Amp High
750 kcmil380.0 mm²475 A13.39 V (5.58%)226.6 V22.09 V (9.2%)8702.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.04 V (4.18%)230.0 V16.56 V (6.9%)6526.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 600 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.02V (2.09%) and delivers 235.0V at the load.

What size aluminum wire is required for 650 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.56V (6.9%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.