🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.34V (5.98%)
Voltage at Load End235.7 VLoss: 4.35 V (4894.9 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2118.32 V (882.63%)0.0 V3494.23 V (1455.93%)2384869.5 WDrop/Amp High
12 AWG3.31 mm²20 A1331.15 V (554.64%)0.0 V2195.77 V (914.9%)1498649.1 WDrop/Amp High
10 AWG5.26 mm²30 A837.66 V (349.03%)0.0 V1381.75 V (575.73%)943066.3 WDrop/Amp High
8 AWG8.37 mm²50 A526.42 V (219.34%)0.0 V868.34 V (361.81%)592655.7 WDrop/Amp High
6 AWG13.3 mm²65 A331.29 V (138.04%)0.0 V546.47 V (227.69%)372972.1 WDrop/Amp High
4 AWG21.15 mm²85 A208.33 V (86.8%)31.7 V343.64 V (143.18%)234540.4 WDrop/Amp High
3 AWG26.67 mm²100 A165.21 V (68.84%)74.8 V272.52 V (113.55%)185996.6 WDrop/Amp High
2 AWG33.62 mm²115 A131.06 V (54.61%)108.9 V216.18 V (90.08%)147547.0 WDrop/Amp High
1 AWG42.41 mm²130 A103.89 V (43.29%)136.1 V171.37 V (71.41%)116966.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A82.37 V (34.32%)157.6 V135.88 V (56.61%)92737.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A65.34 V (27.23%)174.7 V107.79 V (44.91%)73565.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A51.83 V (21.6%)188.2 V85.5 V (35.62%)58352.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A41.1 V (17.13%)198.9 V67.8 V (28.25%)46273.6 WDrop/Amp High
250 kcmil126.7 mm²255 A34.78 V (14.49%)205.2 V57.36 V (23.9%)39151.8 WDrop/Amp High
300 kcmil152.0 mm²285 A28.99 V (12.08%)211.0 V47.82 V (19.92%)32635.1 WDrop/Amp High
350 kcmil177.3 mm²310 A24.85 V (10.35%)215.1 V40.99 V (17.08%)27978.2 WDrop/Amp High
400 kcmil202.7 mm²335 A21.74 V (9.06%)218.3 V35.86 V (14.94%)24472.3 WDrop/Amp High
500 kcmil253.4 mm²380 A17.39 V (7.24%)222.6 V28.68 V (11.95%)19575.9 WDrop/Amp High
600 kcmil304.0 mm²420 A14.49 V (6.04%)225.5 V23.91 V (9.96%)16317.5 WDrop/Amp High
750 kcmil380.0 mm²475 A11.59 V (4.83%)228.4 V19.13 V (7.97%)13054.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.7 V (3.62%)231.3 V14.34 V (5.98%)9789.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 600 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.35V (1.81%) and delivers 235.7V at the load.

What size aluminum wire is required for 650 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.34V (5.98%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.