🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 750 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.7V (17.25%)
Voltage at Load End116.9 VLoss: 3.14 V (2039.5 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 750 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3057.53 V (2547.94%)0.0 V5043.49 V (4202.91%)1987391.3 WDrop/Amp High
12 AWG3.31 mm²20 A1921.35 V (1601.12%)0.0 V3169.32 V (2641.1%)1248874.3 WDrop/Amp High
10 AWG5.26 mm²30 A1209.06 V (1007.55%)0.0 V1994.38 V (1661.99%)785888.6 WDrop/Amp High
8 AWG8.37 mm²50 A759.82 V (633.18%)0.0 V1253.34 V (1044.45%)493879.8 WDrop/Amp High
6 AWG13.3 mm²65 A478.17 V (398.47%)0.0 V788.76 V (657.3%)310810.1 WDrop/Amp High
4 AWG21.15 mm²85 A300.69 V (250.58%)0.0 V496.0 V (413.34%)195450.3 WDrop/Amp High
3 AWG26.67 mm²100 A238.46 V (198.71%)0.0 V393.34 V (327.79%)154997.1 WDrop/Amp High
2 AWG33.62 mm²115 A189.16 V (157.64%)0.0 V312.03 V (260.03%)122955.8 WDrop/Amp High
1 AWG42.41 mm²130 A149.96 V (124.96%)0.0 V247.36 V (206.13%)97471.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A118.89 V (99.08%)1.1 V196.12 V (163.43%)77281.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A94.31 V (78.6%)25.7 V155.58 V (129.65%)61304.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A74.81 V (62.34%)45.2 V123.4 V (102.84%)48626.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A59.33 V (49.44%)60.7 V97.86 V (81.55%)38561.3 WDrop/Amp High
250 kcmil126.7 mm²255 A50.19 V (41.83%)69.8 V82.8 V (69.0%)32626.5 WDrop/Amp High
300 kcmil152.0 mm²285 A41.84 V (34.87%)78.2 V69.02 V (57.51%)27195.9 WDrop/Amp High
350 kcmil177.3 mm²310 A35.87 V (29.89%)84.1 V59.17 V (49.31%)23315.1 WDrop/Amp High
400 kcmil202.7 mm²335 A31.37 V (26.15%)88.6 V51.75 V (43.13%)20393.6 WDrop/Amp High
500 kcmil253.4 mm²380 A25.1 V (20.91%)94.9 V41.4 V (34.5%)16313.2 WDrop/Amp High
600 kcmil304.0 mm²420 A20.92 V (17.43%)99.1 V34.51 V (28.76%)13597.9 WDrop/Amp High
750 kcmil380.0 mm²475 A16.74 V (13.95%)103.3 V27.61 V (23.01%)10878.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.55 V (10.46%)107.4 V20.7 V (17.25%)8158.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 750 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 750 feet one-way at 120V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.14V (2.62%) and delivers 116.9V at the load.

What size aluminum wire is required for 650 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.7V (17.25%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.