⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 750 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.93V (8.62%)
Voltage at Load End202.6 VLoss: 5.43 V (6118.6 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 750 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2647.89 V (1273.03%)0.0 V4367.79 V (2099.9%)2981086.9 WDrop/Amp High
12 AWG3.31 mm²20 A1663.93 V (799.97%)0.0 V2744.71 V (1319.57%)1873311.4 WDrop/Amp High
10 AWG5.26 mm²30 A1047.08 V (503.4%)0.0 V1727.19 V (830.38%)1178832.8 WDrop/Amp High
8 AWG8.37 mm²50 A658.02 V (316.36%)0.0 V1085.42 V (521.84%)740819.7 WDrop/Amp High
6 AWG13.3 mm²65 A414.11 V (199.09%)0.0 V683.08 V (328.41%)466215.1 WDrop/Amp High
4 AWG21.15 mm²85 A260.41 V (125.2%)0.0 V429.55 V (206.51%)293175.4 WDrop/Amp High
3 AWG26.67 mm²100 A206.51 V (99.28%)1.5 V340.64 V (163.77%)232495.7 WDrop/Amp High
2 AWG33.62 mm²115 A163.82 V (78.76%)44.2 V270.23 V (129.92%)184433.7 WDrop/Amp High
1 AWG42.41 mm²130 A129.87 V (62.44%)78.1 V214.22 V (102.99%)146207.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A102.97 V (49.5%)105.0 V169.84 V (81.66%)115921.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A81.68 V (39.27%)126.3 V134.73 V (64.78%)91957.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A64.79 V (31.15%)143.2 V106.87 V (51.38%)72940.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A51.38 V (24.7%)156.6 V84.75 V (40.74%)57842.0 WDrop/Amp High
250 kcmil126.7 mm²255 A43.47 V (20.9%)164.5 V71.7 V (34.47%)48939.7 WDrop/Amp High
300 kcmil152.0 mm²285 A36.23 V (17.42%)171.8 V59.77 V (28.74%)40793.8 WDrop/Amp High
350 kcmil177.3 mm²310 A31.06 V (14.93%)176.9 V51.24 V (24.64%)34972.7 WDrop/Amp High
400 kcmil202.7 mm²335 A27.17 V (13.06%)180.8 V44.82 V (21.55%)30590.3 WDrop/Amp High
500 kcmil253.4 mm²380 A21.73 V (10.45%)186.3 V35.85 V (17.24%)24469.9 WDrop/Amp High
600 kcmil304.0 mm²420 A18.12 V (8.71%)189.9 V29.88 V (14.37%)20396.9 WDrop/Amp High
750 kcmil380.0 mm²475 A14.49 V (6.97%)193.5 V23.91 V (11.49%)16317.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.87 V (5.23%)197.1 V17.93 V (8.62%)12237.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 750 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 750 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.43V (2.62%) and delivers 202.6V at the load.

What size aluminum wire is required for 650 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.93V (8.62%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.