⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.27%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.93V (7.47%)
Voltage at Load End234.6 VLoss: 5.43 V (6118.6 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2647.89 V (1103.29%)0.0 V4367.79 V (1819.91%)2981086.9 WDrop/Amp High
12 AWG3.31 mm²20 A1663.93 V (693.31%)0.0 V2744.71 V (1143.63%)1873311.4 WDrop/Amp High
10 AWG5.26 mm²30 A1047.08 V (436.28%)0.0 V1727.19 V (719.66%)1178832.8 WDrop/Amp High
8 AWG8.37 mm²50 A658.02 V (274.17%)0.0 V1085.42 V (452.26%)740819.7 WDrop/Amp High
6 AWG13.3 mm²65 A414.11 V (172.54%)0.0 V683.08 V (284.62%)466215.1 WDrop/Amp High
4 AWG21.15 mm²85 A260.41 V (108.5%)0.0 V429.55 V (178.98%)293175.4 WDrop/Amp High
3 AWG26.67 mm²100 A206.51 V (86.05%)33.5 V340.64 V (141.94%)232495.7 WDrop/Amp High
2 AWG33.62 mm²115 A163.82 V (68.26%)76.2 V270.23 V (112.59%)184433.7 WDrop/Amp High
1 AWG42.41 mm²130 A129.87 V (54.11%)110.1 V214.22 V (89.26%)146207.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A102.97 V (42.9%)137.0 V169.84 V (70.77%)115921.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A81.68 V (34.03%)158.3 V134.73 V (56.14%)91957.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A64.79 V (26.99%)175.2 V106.87 V (44.53%)72940.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A51.38 V (21.41%)188.6 V84.75 V (35.31%)57842.0 WDrop/Amp High
250 kcmil126.7 mm²255 A43.47 V (18.11%)196.5 V71.7 V (29.88%)48939.7 WDrop/Amp High
300 kcmil152.0 mm²285 A36.23 V (15.1%)203.8 V59.77 V (24.9%)40793.8 WDrop/Amp High
350 kcmil177.3 mm²310 A31.06 V (12.94%)208.9 V51.24 V (21.35%)34972.7 WDrop/Amp High
400 kcmil202.7 mm²335 A27.17 V (11.32%)212.8 V44.82 V (18.67%)30590.3 WDrop/Amp High
500 kcmil253.4 mm²380 A21.73 V (9.06%)218.3 V35.85 V (14.94%)24469.9 WDrop/Amp High
600 kcmil304.0 mm²420 A18.12 V (7.55%)221.9 V29.88 V (12.45%)20396.9 WDrop/Amp High
750 kcmil380.0 mm²475 A14.49 V (6.04%)225.5 V23.91 V (9.96%)16317.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.87 V (4.53%)229.1 V17.93 V (7.47%)12237.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 750 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.43V (2.27%) and delivers 234.6V at the load.

What size aluminum wire is required for 650 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.93V (7.47%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.