🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 2.84%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 5.89V (2.83%)
Voltage at Load End202.1 VLoss: 5.9 V (715.6 W)
Power & Breaker (125%)25.22 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A304.17 V (146.23%)0.0 V501.74 V (241.22%)36878.5 WDrop/Amp High
12 AWG3.31 mm²20 A191.14 V (91.89%)16.9 V315.29 V (151.58%)23174.4 WDrop/Amp High
10 AWG5.26 mm²30 A120.28 V (57.83%)87.7 V198.4 V (95.39%)14583.1 WDrop/Amp High
8 AWG8.37 mm²50 A75.59 V (36.34%)132.4 V124.68 V (59.94%)9164.5 WDrop/Amp High
6 AWG13.3 mm²65 A47.57 V (22.87%)160.4 V78.47 V (37.72%)5767.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.91 V (14.38%)178.1 V49.34 V (23.72%)3626.8 WDrop/Amp High
3 AWG26.67 mm²100 A23.72 V (11.4%)184.3 V39.13 V (18.81%)2876.2 WDrop/Amp High
2 AWG33.62 mm²115 A18.82 V (9.05%)189.2 V31.04 V (14.92%)2281.6 WDrop/Amp High
1 AWG42.41 mm²130 A14.92 V (7.17%)193.1 V24.61 V (11.83%)1808.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.83 V (5.69%)196.2 V19.51 V (9.38%)1434.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.38 V (4.51%)198.6 V15.48 V (7.44%)1137.6 W~ ≤5%
3/0 AWG85.01 mm²200 A7.44 V (3.58%)200.6 V12.28 V (5.9%)902.3 W~ ≤5%
4/0 AWG107.2 mm²230 A5.9 V (2.84%)202.1 V9.74 V (4.68%)715.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A4.99 V (2.4%)203.0 V8.24 V (3.96%)605.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.16 V (2.0%)203.8 V6.87 V (3.3%)504.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.57 V (1.72%)204.4 V5.89 V (2.83%)432.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.12 V (1.5%)204.9 V5.15 V (2.48%)378.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.5 V (1.2%)205.5 V4.12 V (1.98%)302.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.08 V (1.0%)205.9 V3.43 V (1.65%)252.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.66 V (0.8%)206.3 V2.75 V (1.32%)201.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.25 V (0.6%)206.8 V2.06 V (0.99%)151.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 800 feet one-way at 208V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 5.9V (2.84%) and delivers 202.1V at the load.

What size aluminum wire is required for 70 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 5.89V (2.83%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.