🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 250 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.44V (2.68%)
Voltage at Load End238.1 VLoss: 1.95 V (2365.4 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A950.53 V (396.05%)0.0 V1567.92 V (653.3%)1152451.7 WDrop/Amp High
12 AWG3.31 mm²20 A597.31 V (248.88%)0.0 V985.28 V (410.53%)724199.3 WDrop/Amp High
10 AWG5.26 mm²30 A375.87 V (156.61%)0.0 V620.02 V (258.34%)455722.4 WDrop/Amp High
8 AWG8.37 mm²50 A236.21 V (98.42%)3.8 V389.64 V (162.35%)286391.8 WDrop/Amp High
6 AWG13.3 mm²65 A148.65 V (61.94%)91.3 V245.21 V (102.17%)180233.1 WDrop/Amp High
4 AWG21.15 mm²85 A93.48 V (38.95%)146.5 V154.2 V (64.25%)113338.0 WDrop/Amp High
3 AWG26.67 mm²100 A74.13 V (30.89%)165.9 V122.28 V (50.95%)89880.0 WDrop/Amp High
2 AWG33.62 mm²115 A58.81 V (24.5%)181.2 V97.0 V (40.42%)71299.8 WDrop/Amp High
1 AWG42.41 mm²130 A46.62 V (19.42%)193.4 V76.9 V (32.04%)56522.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A36.96 V (15.4%)203.0 V60.97 V (25.4%)44814.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A29.32 V (12.22%)210.7 V48.37 V (20.15%)35549.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.26 V (9.69%)216.7 V38.36 V (15.98%)28197.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.44 V (7.68%)221.6 V30.42 V (12.68%)22361.0 WDrop/Amp High
250 kcmil126.7 mm²255 A15.6 V (6.5%)224.4 V25.74 V (10.73%)18919.5 WDrop/Amp High
300 kcmil152.0 mm²285 A13.01 V (5.42%)227.0 V21.46 V (8.94%)15770.4 WDrop/Amp High
350 kcmil177.3 mm²310 A11.15 V (4.65%)228.8 V18.39 V (7.66%)13520.0 WDrop/Amp High
400 kcmil202.7 mm²335 A9.75 V (4.06%)230.2 V16.09 V (6.7%)11825.8 WDrop/Amp High
500 kcmil253.4 mm²380 A7.8 V (3.25%)232.2 V12.87 V (5.36%)9459.7 WDrop/Amp High
600 kcmil304.0 mm²420 A6.5 V (2.71%)233.5 V10.73 V (4.47%)7885.2 WDrop/Amp High
750 kcmil380.0 mm²475 A5.2 V (2.17%)234.8 V8.58 V (3.58%)6308.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.9 V (1.63%)236.1 V6.44 V (2.68%)4730.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 250 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.95V (0.81%) and delivers 238.1V at the load.

What size aluminum wire is required for 700 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.44V (2.68%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.