⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 450 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.38V (11.15%)
Voltage at Load End117.3 VLoss: 2.7 V (1892.3 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 450 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1975.63 V (1646.36%)0.0 V3258.87 V (2715.72%)1382942.1 WDrop/Amp High
12 AWG3.31 mm²20 A1241.48 V (1034.57%)0.0 V2047.87 V (1706.56%)869039.1 WDrop/Amp High
10 AWG5.26 mm²30 A781.24 V (651.03%)0.0 V1288.68 V (1073.9%)546866.8 WDrop/Amp High
8 AWG8.37 mm²50 A490.96 V (409.13%)0.0 V809.85 V (674.88%)343670.2 WDrop/Amp High
6 AWG13.3 mm²65 A308.97 V (257.48%)0.0 V509.66 V (424.71%)216279.7 WDrop/Amp High
4 AWG21.15 mm²85 A194.29 V (161.91%)0.0 V320.49 V (267.08%)136005.7 WDrop/Amp High
3 AWG26.67 mm²100 A154.08 V (128.4%)0.0 V254.16 V (211.8%)107856.0 WDrop/Amp High
2 AWG33.62 mm²115 A122.23 V (101.86%)0.0 V201.62 V (168.02%)85559.8 WDrop/Amp High
1 AWG42.41 mm²130 A96.89 V (80.75%)23.1 V159.83 V (133.19%)67826.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A76.82 V (64.02%)43.2 V126.72 V (105.6%)53776.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A60.94 V (50.78%)59.1 V100.53 V (83.77%)42659.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A48.34 V (40.28%)71.7 V79.74 V (66.45%)33837.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A38.33 V (31.94%)81.7 V63.23 V (52.69%)26833.2 WDrop/Amp High
250 kcmil126.7 mm²255 A32.43 V (27.03%)87.6 V53.5 V (44.58%)22703.4 WDrop/Amp High
300 kcmil152.0 mm²285 A27.03 V (22.53%)93.0 V44.6 V (37.16%)18924.5 WDrop/Amp High
350 kcmil177.3 mm²310 A23.18 V (19.31%)96.8 V38.23 V (31.86%)16224.0 WDrop/Amp High
400 kcmil202.7 mm²335 A20.27 V (16.89%)99.7 V33.44 V (27.87%)14191.0 WDrop/Amp High
500 kcmil253.4 mm²380 A16.22 V (13.51%)103.8 V26.75 V (22.29%)11351.7 WDrop/Amp High
600 kcmil304.0 mm²420 A13.52 V (11.26%)106.5 V22.3 V (18.58%)9462.2 WDrop/Amp High
750 kcmil380.0 mm²475 A10.81 V (9.01%)109.2 V17.84 V (14.87%)7569.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.11 V (6.76%)111.9 V13.38 V (11.15%)5677.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 450 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 450 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.7V (2.25%) and delivers 117.3V at the load.

What size aluminum wire is required for 700 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.38V (11.15%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.