⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.84V (7.43%)
Voltage at Load End234.6 VLoss: 5.41 V (3784.7 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2634.18 V (1097.57%)0.0 V4345.16 V (1810.48%)1843922.8 WDrop/Amp High
12 AWG3.31 mm²20 A1655.31 V (689.71%)0.0 V2730.49 V (1137.71%)1158718.8 WDrop/Amp High
10 AWG5.26 mm²30 A1041.65 V (434.02%)0.0 V1718.24 V (715.93%)729155.8 WDrop/Amp High
8 AWG8.37 mm²50 A654.61 V (272.75%)0.0 V1079.8 V (449.92%)458226.9 WDrop/Amp High
6 AWG13.3 mm²65 A411.96 V (171.65%)0.0 V679.54 V (283.14%)288372.9 WDrop/Amp High
4 AWG21.15 mm²85 A259.06 V (107.94%)0.0 V427.33 V (178.05%)181340.9 WDrop/Amp High
3 AWG26.67 mm²100 A205.44 V (85.6%)34.6 V338.88 V (141.2%)143808.0 WDrop/Amp High
2 AWG33.62 mm²115 A162.97 V (67.9%)77.0 V268.83 V (112.01%)114079.7 WDrop/Amp High
1 AWG42.41 mm²130 A129.19 V (53.83%)110.8 V213.11 V (88.8%)90435.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A102.43 V (42.68%)137.6 V168.96 V (70.4%)71702.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A81.26 V (33.86%)158.7 V134.03 V (55.85%)56879.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A64.45 V (26.86%)175.5 V106.32 V (44.3%)45116.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A51.11 V (21.3%)188.9 V84.31 V (35.13%)35777.6 WDrop/Amp High
250 kcmil126.7 mm²255 A43.24 V (18.02%)196.8 V71.33 V (29.72%)30271.2 WDrop/Amp High
300 kcmil152.0 mm²285 A36.05 V (15.02%)204.0 V59.46 V (24.78%)25232.6 WDrop/Amp High
350 kcmil177.3 mm²310 A30.9 V (12.88%)209.1 V50.98 V (21.24%)21632.0 WDrop/Amp High
400 kcmil202.7 mm²335 A27.03 V (11.26%)213.0 V44.59 V (18.58%)18921.4 WDrop/Amp High
500 kcmil253.4 mm²380 A21.62 V (9.01%)218.4 V35.67 V (14.86%)15135.6 WDrop/Amp High
600 kcmil304.0 mm²420 A18.02 V (7.51%)222.0 V29.73 V (12.39%)12616.3 WDrop/Amp High
750 kcmil380.0 mm²475 A14.42 V (6.01%)225.6 V23.78 V (9.91%)10093.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.81 V (4.51%)229.2 V17.84 V (7.43%)7569.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 600 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.41V (2.25%) and delivers 234.6V at the load.

What size aluminum wire is required for 700 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.84V (7.43%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.